Laserfiche WebLink
is ♦ L ♦ D ♦ E ♦ F ♦ G <br />Y Y Y p Y Y Y <br />I RELOCATED GENERATOR SET <br />I fi <br />A <br />CP -300 & 1 f <br />PMP -301 1 <br />q , VFD <br />a <br />' Col Sol <br />------=-----PUE (E) TYP ----- �, I <br />y� 1 <br />(E) ACCESS ROAD <br />CONDUIT AND WIRE SCHEDULE <br />CONDUIT <br />CONDUCTOR <br />ID <br />FROM <br />TO <br />NO SIZE <br />NO SIZE <br />4 #3/0 <br />TO NEW PULL BOX NOTEC3 <br />Pot <br />1 31 PVC <br />Ars <br />GENERATOR <br />1 #2 GND <br />P02 <br />1 11 PVC <br />4 #10 PV'R <br />LIGHTING PANEL <br />GENERATOR <br />TO NEW PULL BOX NOTEC3 <br />1 010 GNI <br />3 #ib CNTL <br />MCC <br />FROM EXISTING PANEL <br />P03 <br />1 1' PVC <br />1 #16 GND <br />SECTION /2 <br />MOV -310 <br />BOARD <br />PO4 <br />I 1' PVC <br />6 #10 PCVVER <br />PULL BOX <br />CHEMICAL BLDG <br />1 #1DGND <br />C01 <br />i I' PVC <br />6 #1GN <br />1 #t22 GNDD <br />VFD-301 <br />�c-r,�.r <br />CP -800 <br />PUMP STATUS AND CONTROL <br />ALL INSIDE NEW MCC <br />C21 <br />I 1" PVC <br />4 #14 CNTRL <br />1 #12 GND <br />CP -300 <br />CHEMICAL PUMP <br />CHEMICAL PUMP CONTROL <br />r30 <br />1 1' PVC <br />2 #14 CNTL <br />MeeVFD-301 <br />LOS -31111 <br />#12 GND <br />_-_.. <br />C31 <br />1 I' PVC <br />6 #14 CNTL <br />CP -300 <br />PNL-310 <br />1 #12 GND <br />Sol <br />1 14 PVC <br />3 #18 TSPR <br />1 0126ND <br />Mee- VFD-301 <br />CP -300 <br />ALL INSIDE NEW MCC <br />521 <br />1 I PVC <br />3 #1 B TSPR <br />1 #12 GND <br />CP -300 <br />CHEMICAL PUMP <br />CHEMICAL PUMP CONTROL <br />531 <br />1 1' FMC <br />3 #18 TSPR <br />PNL-310 <br />CP -300 <br />1 #12 GND <br />S51 <br />1 1' PVC <br />i. *18 TSPR <br />CP -300 <br />PIT351 <br />1 #12 GND <br />RELOCATED CHLORINATION <br />FACILITIES <br />0 LOS 301 <br />S21[-C21 <br />PO4 WELL PUMP <br />REVISION <br />DESCRIPTION <br />4c, <br />NEMA <br />3R <br />AREA <br />ENTIRE DRAWING <br />H <br />COUNTY APPROVAL <br />APPROVED BY I DATE <br />NOTES: <br />O1 ONLY NEW CONDUITS ARE SHOWN FOR CLARITY. CONTRACTOR SHALL LOCATE <br />AND PROTECT EXISTING UTILITIES. IF PIPING OR OTHER UTILITIES ARE DAMAGED <br />DURING CONSTRUCTION THEY SHALL BE REPAIRED AT NO COST TO THE OWNER. <br />O2 REPLACE EXISTING PUMP CONTROLS IN MCC SECTION 3/3 WITH NEW VFD PER <br />DWG E-10 AND SPECIFICATION SECTION 16330. EXISTING SECTION IS A 25" GE <br />8000 LINE CAT# 0697XO328LO1 AND MAY NEED TO BE REPLACED (AT NO <br />ADDITIONAL COST) TO HOUSE THE NEW VFD. REMOVED EQUIPMENT TO BE <br />TURNED OVER TO OWNER AND DELIVER TO THEIR DESIGNATED LOCATION. <br />O INTERCEPT EXISTING GENERATOR CONDUITS AND EXTEND TO RELOCATED <br />GENERATOR. INSTALL NEW 13" X 24" ELECTRICAL PULL BOX AS NECESSARY <br />DWG PER E2. PROVIDE AND CONNECT NEW CONDUCTORS FROM LIGHTING PANEL <br />IN MCC AND ATS TO GENERATOR WITHOUT SPLICES. <br />O4 INTERCEPT EXISTING CHEMICAL BUILDING CONDUITS AND EXTEND TO RELOCATED <br />CHEMICAL BUILDING INSTALL NEW 10" X 17" ELECTRICAL PULL BOX AS <br />NECESSARY, INSTALL PER E2. PROVIDE AND CONNECT NEW CONDUCTORS FROM <br />LIGHTING PANEL IN MCC TO CHEMICAL BUILDING WITHOUT SPLICES. <br />OS CONNECT NEW CONDUIT PO4 TO THE EXISTING J -BOX. A NEW WP J -BOX IS <br />REQUIRED FOR CONDUITS C&S21. PROVIDE AN ADDITIONAL WP J -BOX ON THE <br />INSIDE OF THE CHEMICAL BUILDING TO PROVIDE FOR 2 %" WEATHER PROOF <br />CORD GRIPS FOR CONTROL WIRING TO NEW CHEMICAL PUMP. <br />© PROVIDE NEW 20A 120VAC SINGLE RECEPTACLE CONNECTED TO LP CKT #7 FOR <br />THE NEW CHEMICAL PUMP. <br />O7 NEW LOCK OUT STOP (LOS). INSTALL PER F/E2. <br />O ALL EQUIPMENT FED FROM PNL-310 PRE -WIRED BY SIEMENS <br />�OQWpF ESS/LLIpy�l <br />CASSIITY <Cy� <br />h Z <br />W E-17132 m <br />_ <br />Or Ezp. 09/30/07 <br />sT otic N(IP� �* <br />9TFOF CAI <br />ELECTRICAL SITE PLAN <br />SCALE: 1"=5'-O" <br />i iECO1 IDP b 1t ING <br />Any i" �� 7r, Uoi�l� "It, Is U,awing Should Verify <br />A,I II1fCrIT!atIO11 BV IrISDPCflnri Thn Q;+_ n<u;__.. <br />RECORD DRAWING <br />These record drawings have been prepared <br />based on information provided by others. <br />The Engineer has not verified the accuracy <br />of such information and shall not be resp- <br />onsible for any errors or omissions which <br />may be incorporated herein as a result. <br />SCALE BAR IS ONE INCH DATE <br />AT FULL SCALE DESIGNED RE ECO: 0GIC FLYING J INC. FLYING J-LODI <br />DRAWING NUMBER SHEET NUMBER <br />AS NOTED D JULY 2007 IF NOT ONE 1DRAWN BD 333 WEST CENTER STREET <br />ON THIS SHEET FILE Engineering CSA 31 WELL NUMBER 3 NITRATE ELECTRICAL SITE PLAN AND CONDUIT SCHEDULE E11 <br />SCALE ACCORDINGLY FLYJ07-007 CHECKED FJF Rocklin, California NORTH SALT LAKE, UT 84054 TREATMENT SYSTEM SITE IMPROVEMENTS 15 OF 22 <br />P, <br />. L <br />I� <br />12 <br />11 <br />