CONTINUED FROM PG E23 <br />ALARMS—DISCRETE POINTS (DISPLAY AT OIZHMI) <br />(The following alarm points are typ. for all pumps) <br />—Pump motor high temperature shutdown <br />—Pump fail—to—run alarm <br />—Pump high discharge pressure <br />(Note: All alarms belonging to other site PLCs will also be displayed at OID of each site PLC for monitorning only) <br />(The following alarm points are for the (N) storage tank) <br />—(N) Storage tank high—high /eve/ alarm ( ) <br />—(N) Storage tank ank low—low /eve/ alarm ( ) AD — H/ TANK +DOX-007T <br />DO -007 <br />ALARMS—ANALOG SET POINTS (DISPLAY AT 0/D/HMl) <br />—(N) Storage tank level high (>_ ) AD2 — LO TANK <br />—(N) Storage tank low level (<_ ) DO -008 DOX-008 T <br />—(N) Storage tank level transmitter out of range: Low (<4mA) / High (>20mA) <br />BOOSTER PUMP MODE — SENT VIA ETHERNET. <br />(N) BOOSTER PUMP CONTROL LOGIC. D03 — HI SYSTEM PRESSURE DOX-009 T <br />Each pump shall be controlled by the PLC (N) Booster Pump Control Logic, when the pumps H01 switch is in the <br />Auto" position and the "New Mode" is 'Enabled' through the O/D or (F) HMI. Under the conditions the control logic <br />shat/ start and stop the pumps based on the pressure values in the distribution system as determined by the AD4 — LO SYSTEM PRESSURE <br />distribution system pressure transmitter. The control logic shall start the lead pump at 40 psi, th : lag at 35 psi, DO -010 + DOX-010 T <br />and the log—lag at 30 psi on falling pressure. On rising pressure, turn off the lag—log pump at JO psi, the lag at <br />55 psi, and the lead at 60 psi. The control logic shall start an internal timer when the lead pump has shutdown on TO AUTOD/ALER <br />rising pressure. The pumps shall be locked out from restarting until this timer has completed its `iming cycle. Timer <br />shall be adjustable from 0-99 minutes with initial setting to be 10 minutes. AD5 —CHL. RESID. Hl +DOX-011 T <br />DO -011 <br />The control logic shall monitor to distribution system low pressure switch from the well PLC (PLC- 2) via Ethernet and <br />shall override the above control logic to run all pumps when the low pressure switch has activated and shall utilize AD6 —CHL. RESID. LO <br />the shutoff points from the distribution pressure transmitter as described above.. The override cor,,rol described here DO -012 DOX-012T <br />shall override the restart time lock. <br />(N) CHLORINE INJECTION CONTROL <br />—LO TANK <br />Chlorine injection shall be controlled by the PLC using a PID loop with <br />the Chlorine Residual Ano/y,,er (AIT1) as the <br />AD7 — XXX <br />DOX-013'x' <br />monitoring device. The PLC shall accept an Operator Settable Set point <br />via the O/D & (F) HMI for desired dosing. The <br />DO -013 <br />T <br />PLC shall send a pacing signal to the Chlorine Metering Pump (MPI) in order to maintain the desired set point <br />0 <br />W <br />against the measured chlorine residual value. The PLC shall produce a <br />Deviation from set point alarm at t or — <br />n. <br />Q <br />___mg/L of the set point. <br />W <br />Q <br />AD8 — XXX <br />J1 <br />DOX-014 <br />Z <br />Z <br />0 <br />DO -014 <br />T <br />(N) SEQUESTERING CONTROL <br />0- <br />0. <br />thU <br />A sequestering agent is to be injected into the effluent flow from the <br />storage tank, paced from , 7e outlet flow, using <br />0 <br />z <br />the flowmeter on the effluent side of the tank. <br />FLOW METER LOGIC: <br />Total volume of water pumped is calculated on hourly, daily and weekly basis from flow meter analogue input. Set <br />flow value to zero and stop integration of flow inputs when flow drops to an adjustable low flow cut off value. <br />STATUS POINT (DISPLAY AT OID/HMI) <br />(The following status points are typ. <br />— ATS in normal position <br />— ATS in emergency position <br />— Generator running indication <br />OUTPUTS TO AUTODIALER <br />—HI TANK <br />—LO TANK <br />—HI SYSTEM <br />PRESSURE <br />—LO SYSTEM <br />PRESSURE <br />—CHL. RESID. <br />HI <br />—CHL. RESID. <br />LO <br />h <br />I <br />ZS <br />for the ATS & generator) <br />CONTINUED TO PG E25 <br />WELL SI TE <br />,eSOFESS/O� <br />�= <br />10246 <br />Elq� SEPT. <br />\k<«eal En4�� <br />�Ah'W mvjdo%i <br />en I e r jcF6a@ <br />INC. <br />6060 Sunrise Vista, #3450 <br />Citrus Heights, ca 95610 <br />COPYRIGHTO 2095 NORTHSTAR ENGINEERING GROUP, INC <br />• <br />0 <br />W <br />0 <br />W <br />IL <br />n. <br />Q <br />W <br />Q <br />0 <br />Z <br />Z <br />0 <br />in <br />w z <br />� o <br />0- <br />0. <br />thU <br />W <br />0 <br />0 <br />z <br />W Q <br />z <br />O 0 <br />O <br />V9 <br />O. ::j <br />U <br />Z <br />Q <br />H <br />U_ <br />LU <br />o <br />O <br />O <br />Jn <br />H <br />z <br />LU <br />O <br />Z <br />O 0 <br />Z 0 <br />C <br />O z <br />2 Q <br />~ U) <br />b <br />JOB <br />DATE: <br />03 0B 07 <br />SCALE: <br />DRAWN: K.T. <br />DESIGN: M.B. <br />CHK D: <br />M.B. <br />SHEET <br />NUMBER <br />E24 <br />DF 47 <br />