Laserfiche WebLink
(E)JOINT POLE <br />PARTIAL ELECTRICAL SINGLE LINE DIAGRAM <br />NOT TO SCALE <br />4 SWITCHGEAR'MS' <br />V, 3PH, 4W <br />IT ELECT ROOM) <br />3G <br />GENERAL NOTES <br />1. AT ALL TIMES THE CONTRACTOR WILL BE SOLELY AND COMPLETELY RESPONSIBLE FOR <br />"^SWAY <br />)LE PHASE CONDUCTORS <br />NEUTRAL. WRAP WITH <br />EVERY 36" ON CENTER. <br />GROUND WIRE <br />SEGREGATED FROM AND NOT <br />INTERTWINED WITH NEUTRAL <br />OR PHASE CONDUCTORS. <br />SEGREGATED GROUND WIRE <br />INSTALLATION DETAIL <br />NOT TO SCALE <br />t z rre. ns icy .{�vv"� <br />Any 'erszt> .;Sine 'hi .;wi­�, Sh,, Id Ve <br />At- ,urma, .n 6y li.:,pecting The Site Of i4 k <br />SYMBOL LIST <br />5�91� RECESSED FLUORESCENT FIXTURE TYPE A - SEE FIXTURE SCHEDULE <br />FTBM FLUORESCENT FIXTURE TYPE B MOUNTED ON WALL AT +90" ABOVE FLOOR - SEE FIXTURE SCHEDULE <br />_ilS 1 PST LIGHT SWITCH, 20A, 125/277V RATED, +48", LETTER DENOTES OUTLETS CONTROLLED <br />SM MANUAL MOTOR STARTING SWITCH, HORSE POWER RATED WITH OVERLOADS <br />❑ JUNCTION BOX - SIZE PER CODE <br />20A, 125V, 3W, SPECIFICATION GRADE, GROUNDED DUPLEX RECEPTACLE, +24" U.O.N. <br />20A, 125V, 3W, SPECIFICATION GRADE, GROUNDED DUPLEX RECEPTACLE, +48", GFI TYPE <br />PfF 20A, 125V, 3W, SPECIFICATION GRADE, GROUNDED DOUBLE DUPLEX RECEPTACLE, +24" U.O.N. <br />WELDER OUTLET, 480V 3-1, 3W, 60A WITH INTERLOCKED DISCONNECT SWITCH. SEE SPECIFICATIONS <br />Q 4"SQ X 2-1/8"D TELEPHONE/DATA J -BOX, +18" WITH 1" CONDUIT UP TO TRUSS SPACE <br />MOTOR OUTLET, HORSEPOWER NOTED, COMPLETE WITH CONNECTIONS AND FLEX <br />❑T TRANSFORMER, KVA AND VOLTAGE AS SHOWN IN CONNECTION DETAILS <br />❑J NON-FUSED DISCONNECT SWITCH, 30A, 3 POLE, 480 VOLT NEMA 3R, OR AMP RATING NOTED <br />Eli FUSED DISCONNECT SWITCH, 30A, 3 POLE, 480 VOLT NEMA 3R OR AMP RATING NOTED <br />(�)1 COMBINATION FUSIBLE SWITCH MOTOR STARTER, NEMA SIZE 1 OR AS NOTED. ENCLOSURE <br />SHALL BE NEMA 12 WITH H -O -A SELECTOR SWITCH AND 120 VOLT 100VA CONTROL TRANSFORMER <br />I° ESD FUEL SYSTEM'EMERGENCY SHUT DOWN'. DEVICE SHALL BE LISTED FOR CLASS 1, DIV 1 <br />�\OSIP/F FUSED SWITCH - SIZE /POLE/FUSE NOTED <br />- Io - CIRCUIT BREAKER - TRIP/POLE/FRAMED NOTED <br />T/P/F <br />EXISTING CONDUIT <br />CONDUIT EXPOSED ON WALL OR IN CEILING <br />HOMERUN TO PANEL BOARD OR OTHER TERMINATION POINT <br />ANY BRANCH CIRCUIT CONDUIT SHALL BE MINIMUM 3/4"C - 2912 UNLESS OTHERWISE NOTED <br />OR INDICATED. FOR A GREATER NUMBER OF #12 WIRES: ( +H- = 3/4'C - 3#12) ETC. <br />FOR WIRE SIZES OTHER THAN #12: 3#12 IN CODE SIZE CONDUIT) ETC. <br />--� HOT WIRES <br />NEUTRAL <br />e ISOLATED GROUND <br />—�� CONDUIT SEAL <br />BC BARE COPPER <br />C CONDUIT <br />(E) EXISTING <br />(X) REMOVE ITEM NOTED <br />(R) RELOCATED AND RECONNECTED DEVICE <br />U.O.N. UNLESS OTHERWISE NOTED <br />WP WEATHERPROOF <br />EP EXPLOSION PROOF FITTING <br />ESD EMERGENCY SHUT DOWN <br />O SHEET NOTE <br />1 DETAIL 1 <br />E1 SHEET WHERE DETAIL IS DRAWN <br />NO NORMALLY OPEN <br />NC NORMALLY CLOSED COUNTY OF SAN JOAQUIN <br />4q--- GROUNDING ROD Submitted 2008 <br />THOMAS RYAN FLINN <br />DIRECTOR OF PUBLIC WORKS <br />1 ADDED PRIORITY PANEL TM 3/08 <br />0 PRELIMINARY FOR CLIENT REVIEW TM <br />REV. I DESCRIPTION BY DATE <br />ON JOAQUIN COUNTY e PUBLIC WOKS <br />STOCKTON, CA <br />T. OTOELLENGINEERS UAKLAND CALIFORNIA <br />SCALE AS NOTED IFOR <br />0 <br />THE USE OF THESE DRAWINGS AND CHECKED TM <br />SPECIFICATIONS SHALL BE RESTRICTED TO <br />THE ORIGINAL USE FOR WHICH THEY WERE gPPROVED <br />PREPARED. REUSE, REPRODUCTION, OR <br />PUBLICATION, IN WHOLE OR IN PART, IS <br />'ROHIBITED WITHOUT THE WRITTEN CONSENT ,708 <br />OF T. MITCHELL ENGINEERS. OJ2� <br />CNG SYSTEM UPGRADE <br />DOWNTOWN GARAGE <br />TITLE <br />ELECTRICAL - SYMBOLS, NOTES, <br />DIAGRAM & DETAILS <br />DWG. NO. El <br />CONDITION OF JOB SITE, INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY <br />SHEET NOTES <br />AND FOR ALL NECESSARY INDEPENDENT ENGINEERING REVIEWS OF THESE <br />CONDITIONS. THE ENGINEERS JOB SITE REVIEW IS NOT INTENDED TO INCLUDE REVIEW <br />ALL NEW EQUIPMENT CIRCUIT BREAKERS SHALL HAVE <br />OF THE ADEQUACY OF THE CONTRACTORS SAFETY MEASURES. <br />O ATTACHMENTS TO ALLOW FOR PADLOCK OFF DEVICE. <br />2. <br />THE CONTRACTOR SHALL MAKE AN EXAMINATION OF THE SITE. HE SHALL COMPARE <br />THE SITE WITH THE DRAWINGS AND SPECIFICATIONS AND SATISFY HIMSELF AS TO <br />pp� <br />CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED, HE SHALL ASCERTAIN AND <br />EMERGENCY SHUT DDOWN SHALL STOP COMPRESSORS. SHUT <br />CHECK THE LOCATIONS OF ANY EXISTING STRUCTURES OR EQUIPMENT WHICH MAY <br />j/ DOWN BUTTON SHALL BE SIMILAR TO ALLEN -BRADLEY <br />AFFECT THIS WORK, NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE IN HIS BEHALF <br />BULLETIN SOON FOR <br />RCL <br />R CLASS 1 DIV 1 LOCATIONS. MUSHROOM PUSHBUTTON <br />HRO120V <br />FOR ANY EXPENSE TO WHICH HE MAY BE PUT DUE TO FAILURE OR NEGLECT ON HIS <br />HAVE 2-N.C. AND CONTACTS SHALL BE RATED 4 <br />PART TO MAKE SUCH EXAMINATION. <br />AMPS. COORDINATE WITH COMPRESSOR DRAWINGS. <br />3. <br />ALL WORK SHALL BE COORDINATED WITH THE OWNER TO MAINTAIN CONTINUITY OF <br />O 3 -POLE NON -FUSIBLE SERVICE DISCONNECT <br />SERVICE AND MAXIMUM UTILIZATION OF THE OWNERS FACILITY. ALL WORK SHALL BE <br />CLASS 1, DIV 2 ENCLOSURE. <br />BID ON A WORMAL TIME BASIS WITH PREMIUM TIME IN ADDITION ONLY AS AUTHORIZED <br />HUBBELL XEDS-100AA. <br />FOR CORE BORING OR OTHER WORK WHICH WILL BE NOISY, DIRTY OR OTHERWISE <br />THE WORK PROCESS. <br />OOBSTRUCT <br />q DISCONNECT AND REMOVE EXISTING CONDUCTORS FROM <br />ELECTRICAL ROOM TO COMPRESSOR AREA. REROUTE EXISTING <br />4. <br />THE CURRENT ISSUE OF ALL NEPA, CEC, CBC, UBC, UFC, ANSI, OSHA, ASTM, NEMA, AND <br />CONDUIT AS NEEDED AND PROVIDE NEW RIGID STEEL RISER AT NEW <br />OTHER NATIONALLY PUBLISHED CODES OR STANDARDS SHALL APPLY TO THIS WORK <br />PULL NEW CONDUCTORS AS SHOWN. <br />WHETHER ADOPTED BY LOCAL AGENCIES OR NOT. THE MOST STRINGENT CODE SHALL <br />I PROVIDE AND INSTALL NEW ESD PUSHBUTTONS AND FLAMABLE GAS DETECTORS <br />APPLY. <br />N AS SHOWN ON DRAWING P-2. TIE ALL PUSH BUTTONS AND GAS DETECTOR ALARM <br />5. <br />NOTHING IN THE DRAWING OR SPECIFICATIONS INTENDED TO ALLOW A VIOLATION OF <br />OUTPUTS INTO ESD CIRCUIT OF NEW CNG COMPRESSOR TO SHUT DOWN COMPRESSOR <br />ELECTRICAL WORKING SPACE AROUND ELECTRICAL EQUIPMENT. A 30V MIN x 48"D x <br />SHUT DOWN POWER TO DISPENSER, AND STOP FLOW OF GAS TO DISPENSERS AND <br />6'-6"H SPACE SHALL BE CLEAR TO THE FLOOR IN FRONT OF ALL ELECTRICAL PANELS, <br />TIMEFILL STATIONS UPON ACTIVATION OF ESD. TIE NEW GAS DETECTORS INTO EXISTING <br />CONTROLS OR ITEMS THAT REQUIRE MAINTENANCE OR ACCESS WHILE ENERGIZED. <br />120V CIRCUIT FEEDING EXISTING DETECTORS. <br />ANY DEVIATION FROM THIS MINIMUM SHALL BE APPROVED, IN WRITING. <br />© PROVIDE AND INSTALL 3/4"X10' GROUND ROD IN COMPRESSOR AREA FOR EQUIPMENT GROUND. <br />TIE COMPRESSOR, AND DRYER TO GROUND ROD WITH #2 INSULATED GROUND CONDUCTOR. <br />6. <br />ALL CONDUITS SHALL RUN TIGHT TO SLAB AND BEAMS. WHERE DUCTWORK IS <br />INSTALLED TIGHT TO SLAB, RUN CONDUIT BELOW DUCTS AS TIGHT TO DUCTS AS <br />O ROUTE SPARE CONDUITS FROM NEW COMPRESSOR TO ELECT ROOM FOR FUTURE PHONE <br />POSSIBLE. <br />AND SIGNAL WIRING. <br />7. <br />DO NOT SUPPORT CONDUITS FROM DUCTS, MECHANICAL SUPPORTS OR EQUIPMENT <br />O MAX FILL FOR CONDUIT SEAL -OFF FITTINGS EQUALS 25% (40%ALOWED FOR CONDUIT). <br />OF ANY KIND. <br />ADJUST SIZE ACORDINGLY. <br />8. <br />ALL CABLES, CONDUITS, PIPING OR EQUIPMENT LOCATIONS AND ELEVATIONS ARE <br />O REFER TO DRAWING P-2 AND CHAPTER 500 OF NEC FOR EXTENT OF CLASSIFIED AREAS <br />APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR FIELD CHECKING AND MAKING <br />ALL NECESSARY OFFSETS, AS REQUIRED, TO AVOID EXISTING INTERFERENCES AND <br />COORDINATE WITH OTHER TRADES. <br />9. <br />IDENTIFY EACH CONDUCTOR BY SHRINK -ON INDELIBLY MARKED BRADY-TAGS AND <br />EACH ELECTRICAL ITEM BY BLACK - WHITE - BLACK ENGRAVED SCREW - ON PLASTIC <br />NAMEPLATE, LEGEND PER DRAWING. <br />LOAD SUMMARY <br />10. <br />ALL GROUND WIRES SHALL BE SEGREGATED FROM PHASE CONDUCTORS IN CONDUITS <br />TO MINIMIZE GROUND LOOPS. <br />COMPRESSOR C-1 (52 FLA) = 43 KVA <br />11. <br />ELECTRICAL DESIGN BASED UPON TYPICAL VENDOR EQUIPMENT. COORDINATE FINAL <br />COMPRESSOR CONTROL = 3KVA <br />INSTALLATION WITH ACTUAL EQUIPMENT FURNISHED. <br />GAS DRYER = 1KVA <br />LARGEST MOTOR X 25% = 11 HP <br />12. <br />THE CONTRACTOR SHALL PROVIDE ALL FUSES REQUIRED FOR PROJECT POWER <br />INCLUDING ANY FUSES BLOWN DURING INITIAL TESTING. <br />58KVA = 70A AT3PH <br />CIRCUIT <br />10000 AMPP CIRCUIT OKAY <br />13, <br />BONDING JUMPERS SHALL BE INSTALLED TO INSURE CONTINUITY WHERE CONDUIT <br />CONNECTIONS AT CONCENTRIC KNOCKOUTS ARE TO SERVE AS A GROUND, <br />14. <br />ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGES TO ALL WALLS, <br />FLOORS AND PAVING. IF DAMAGE OCCURS DURING CONSTRUCTION. THEY SHALL <br />COORDINATE WITH OWNER TO PATCH, PAINT AND REPAIR TO MATCH EXISTING <br />CONDITIONS. <br />"^SWAY <br />)LE PHASE CONDUCTORS <br />NEUTRAL. WRAP WITH <br />EVERY 36" ON CENTER. <br />GROUND WIRE <br />SEGREGATED FROM AND NOT <br />INTERTWINED WITH NEUTRAL <br />OR PHASE CONDUCTORS. <br />SEGREGATED GROUND WIRE <br />INSTALLATION DETAIL <br />NOT TO SCALE <br />t z rre. ns icy .{�vv"� <br />Any 'erszt> .;Sine 'hi .;wi­�, Sh,, Id Ve <br />At- ,urma, .n 6y li.:,pecting The Site Of i4 k <br />SYMBOL LIST <br />5�91� RECESSED FLUORESCENT FIXTURE TYPE A - SEE FIXTURE SCHEDULE <br />FTBM FLUORESCENT FIXTURE TYPE B MOUNTED ON WALL AT +90" ABOVE FLOOR - SEE FIXTURE SCHEDULE <br />_ilS 1 PST LIGHT SWITCH, 20A, 125/277V RATED, +48", LETTER DENOTES OUTLETS CONTROLLED <br />SM MANUAL MOTOR STARTING SWITCH, HORSE POWER RATED WITH OVERLOADS <br />❑ JUNCTION BOX - SIZE PER CODE <br />20A, 125V, 3W, SPECIFICATION GRADE, GROUNDED DUPLEX RECEPTACLE, +24" U.O.N. <br />20A, 125V, 3W, SPECIFICATION GRADE, GROUNDED DUPLEX RECEPTACLE, +48", GFI TYPE <br />PfF 20A, 125V, 3W, SPECIFICATION GRADE, GROUNDED DOUBLE DUPLEX RECEPTACLE, +24" U.O.N. <br />WELDER OUTLET, 480V 3-1, 3W, 60A WITH INTERLOCKED DISCONNECT SWITCH. SEE SPECIFICATIONS <br />Q 4"SQ X 2-1/8"D TELEPHONE/DATA J -BOX, +18" WITH 1" CONDUIT UP TO TRUSS SPACE <br />MOTOR OUTLET, HORSEPOWER NOTED, COMPLETE WITH CONNECTIONS AND FLEX <br />❑T TRANSFORMER, KVA AND VOLTAGE AS SHOWN IN CONNECTION DETAILS <br />❑J NON-FUSED DISCONNECT SWITCH, 30A, 3 POLE, 480 VOLT NEMA 3R, OR AMP RATING NOTED <br />Eli FUSED DISCONNECT SWITCH, 30A, 3 POLE, 480 VOLT NEMA 3R OR AMP RATING NOTED <br />(�)1 COMBINATION FUSIBLE SWITCH MOTOR STARTER, NEMA SIZE 1 OR AS NOTED. ENCLOSURE <br />SHALL BE NEMA 12 WITH H -O -A SELECTOR SWITCH AND 120 VOLT 100VA CONTROL TRANSFORMER <br />I° ESD FUEL SYSTEM'EMERGENCY SHUT DOWN'. DEVICE SHALL BE LISTED FOR CLASS 1, DIV 1 <br />�\OSIP/F FUSED SWITCH - SIZE /POLE/FUSE NOTED <br />- Io - CIRCUIT BREAKER - TRIP/POLE/FRAMED NOTED <br />T/P/F <br />EXISTING CONDUIT <br />CONDUIT EXPOSED ON WALL OR IN CEILING <br />HOMERUN TO PANEL BOARD OR OTHER TERMINATION POINT <br />ANY BRANCH CIRCUIT CONDUIT SHALL BE MINIMUM 3/4"C - 2912 UNLESS OTHERWISE NOTED <br />OR INDICATED. FOR A GREATER NUMBER OF #12 WIRES: ( +H- = 3/4'C - 3#12) ETC. <br />FOR WIRE SIZES OTHER THAN #12: 3#12 IN CODE SIZE CONDUIT) ETC. <br />--� HOT WIRES <br />NEUTRAL <br />e ISOLATED GROUND <br />—�� CONDUIT SEAL <br />BC BARE COPPER <br />C CONDUIT <br />(E) EXISTING <br />(X) REMOVE ITEM NOTED <br />(R) RELOCATED AND RECONNECTED DEVICE <br />U.O.N. UNLESS OTHERWISE NOTED <br />WP WEATHERPROOF <br />EP EXPLOSION PROOF FITTING <br />ESD EMERGENCY SHUT DOWN <br />O SHEET NOTE <br />1 DETAIL 1 <br />E1 SHEET WHERE DETAIL IS DRAWN <br />NO NORMALLY OPEN <br />NC NORMALLY CLOSED COUNTY OF SAN JOAQUIN <br />4q--- GROUNDING ROD Submitted 2008 <br />THOMAS RYAN FLINN <br />DIRECTOR OF PUBLIC WORKS <br />1 ADDED PRIORITY PANEL TM 3/08 <br />0 PRELIMINARY FOR CLIENT REVIEW TM <br />REV. I DESCRIPTION BY DATE <br />ON JOAQUIN COUNTY e PUBLIC WOKS <br />STOCKTON, CA <br />T. OTOELLENGINEERS UAKLAND CALIFORNIA <br />SCALE AS NOTED IFOR <br />0 <br />THE USE OF THESE DRAWINGS AND CHECKED TM <br />SPECIFICATIONS SHALL BE RESTRICTED TO <br />THE ORIGINAL USE FOR WHICH THEY WERE gPPROVED <br />PREPARED. REUSE, REPRODUCTION, OR <br />PUBLICATION, IN WHOLE OR IN PART, IS <br />'ROHIBITED WITHOUT THE WRITTEN CONSENT ,708 <br />OF T. MITCHELL ENGINEERS. OJ2� <br />CNG SYSTEM UPGRADE <br />DOWNTOWN GARAGE <br />TITLE <br />ELECTRICAL - SYMBOLS, NOTES, <br />DIAGRAM & DETAILS <br />DWG. NO. El <br />