General Notes <br />I. Interpretation of drawings specifications <br />A) For convenience, specification have been prepared for this protect and are <br />arranged in -several sections, but such separation shall not be considered as the <br />limits of the work required by any separate trade. The terms and conditions of <br />such limitations are wholly between the contractor and his subcontractors. <br />B) In general, the working details will indicate dimensions, positions and kind of <br />construction, and the specifications, qualitle5 and methods. Any work Indicated on <br />the working detolls mentionedbut not in the specifications, or vice versa, shall be <br />furnished as though fully set forth In both. Work not particularly detailed, marked or <br />specified, shall be the same as simllar parts that are detailed, marked or <br />specified. If conflicts occur between drawings and specifications, the most <br />expensive materials or methods will prevail. <br />G) Should an error wear In the working details or�seclficatlonor in work done by <br />others af�cting this work, the contractor shall notify the architect at once and In <br />wry IF the Contractor proceeds with the work 5c affected without having given <br />such written notice and without receiving the necessary approval, decision or <br />instruction in writing from the owner, then he shall have no valid claim against the <br />owner, for the cost of 5o proceeding and shall make good any resulting damage or <br />defect. No verbal approval, decision, or Instruction shall be valid or be the basis <br />For any claim against the owner, Its officers, employees or agents. The Foregoing <br />includes typical errors In the specifications or notational errors In the working <br />details where the interpretations IS doubtful or where the error Is 5ufficlently <br />apparent as to place a reasonably prudent contractor on notice that, should he <br />elect to proceed, he 15 Joing so at his own risk. <br />2. Construction shall conform to all applicable codes and regulations. <br />3. shop Drawing Note, <br />A) Shop drawings shall be submitted In the Form of one septa transparency and two <br />blue line prints of each sheet. <br />B) The purpose of shop drawings submittals by the Contractor Is to demonstrate to <br />the 5tructura/ Engineer that he understands the design concept by Indicating which <br />materials he Intends to Furnish and Install, and by detailing the fabrication and <br />Installation methods he intends to use. <br />G) Prior to fabrication, shop drawings shall be submitted for review to the structural <br />Engineer. Shop drawings submittals shall Include, but are not nece55arlly limited to <br />structural steel, reinforcing steel, and glued laminated beams. <br />D) Prior to submission the Contractor shall review all submittals for conformance with <br />the contract documents and shall stamp submittals as being "Reviewed For <br />Conformance': <br />E) Shop drawing submittals processed by the Structural Engineer are not change orders. <br />F) Any detail on the shop drawing that deviates from the contract documents shall <br />clearly be marked with the note "This I5 a Change ". <br />6) Shop draw/nay or ca/culotlon5 submitted For review that reQulre resubmittal for <br />re -review shall be billed hourly For such time to the 6ene_rol Contractor. Re-revlew <br />will not proceed without written approval from the General Contractor for <br />additional engineering review services. <br />4. safety Note: <br />A) It Is the Contractors responsibility to comply with the pertinent sections, as they <br />apply to this project, of the "Construction Safety Orders" Issued by the State of <br />California latest edition, and a// 05NA requirements. <br />B) The owner and the Structural Engineer do not accept any respon5lbJlity for the <br />6ontractor5 failure to comply with these requirements. <br />G) The Contractor shall be responsible For adequate desla_ n and construction of all <br />forms and 5hortno re ulred. <br />5. The ContractI n I Architect nd 5tructural Engineer where a conflict ora <br />dI�oncy occurs between the structural drowinas and any other portlon of the contract <br />documents or existing Field conditions. Such notlficatlon shall be given In due time so <br />as not to affect the constructlon schedule. In case of a conflict between structural <br />drawings and specifications, the more restrictive condition shall take precedence <br />unless written approval has been given for the least restrictive. Contractor shall verify <br />all dimensions with architectural and structural drawings prior to commencing any work. <br />6. Where no specific detail is shown, the construction shall be Identical or similar to that <br />Indicated for like cases of construction on this project. Should there be any question, <br />contact the Architect and Structural Engineer prior to proceeding. <br />7. When construction attaches to on existing building, a complete set of drawings of the <br />existingg building shall be kept on the Job site. Contractor to obtain these drawings <br />Prom the owner. <br />8. Contractor shall provide an allowance equal to 256 of the bid For structural steel, misc. <br />Iron and reinforcing steel to be used at the discretion of the structural engineer. <br />Unused amount to revert to the owner upon completion of the Job. <br />q. Any substitutions for -structural members, hardware, or details shall be reviewed by the <br />Architect and Structural Engineer. Such review w111 be billed on a time and materials <br />basis to the General Contractor with no guarantee that the substitution will be allowed. <br />l0. Do not scale drawings. Contact the Architect or 5tructura/ Engineer for any dimension <br />not shown. <br />!l. These drawings are not complete until reviewed and accepted by local building <br />officials and signed by the owner and the 5tructura/ Engineer. <br />12. All drawings and written material appearing herein constitutes the original and <br />unpublished work of the 5tructura/ Engineer and the same may not be duplicated, used <br />or disclosed without written consent of the Structural Engineer and compensation. <br />l3. The structure shown on these drawings /5 structurally sound only in Its completed form. <br />The stability of this structure depends on the diaphragm and the bracing members shown. <br />The Contractor 15 to provide for the design and construction of shoring for all earth, <br />forms, concrete, steel, wood, and masonry to resist gravity, earth, wind, seismic, and <br />construction loads. 5horing shall remain In place until all diaphragm and lateral <br />resisting elements are In place In their entirety. <br />Des lan Criteria <br />I. Godes and Standards 2. Vertical Loads: <br />2001 Gallfornia Bvlldtng Code Roof Live Load = 16 psf (reducible) <br />3. Lateral Loads: <br />5elsmic: <br />Zone 3, Z= 0.3 <br />R= 4.5 <br />z= /.a <br />NQ= n/a <br />N„= n/a <br />6, = 0.36 <br />G„ = 0.54 <br />Wind: <br />75 mph, exposure C <br />Foundatlons <br />4. 5olls Values: <br />Allowable soil pressures: <br />1. DL = 1000 psf <br />3. DL+LL+Seismic= 1330 psf <br />minimum depth= 12" <br />minimum width= 12" <br />I. All foundation work shall be done In accordance with the requirements of the -soils <br />report. <br />2. Foundation depths Indicated on plans are for e5tlmotingg purposes only. Actual depths <br />are to be determined by a Geotechnical Engineer on the, Jobslte. <br />3. Bottoms of a// foundations shall be level. Changes In bottom of foundation elevation <br />shall be made according to stepped footing detail on the Typical Detall sheet. <br />4. All pile caps, grade beams, tle beams e other 2x/2 1x8 2x12 <br />footing5 shall be Formed unless specifically <br />approved by the 5tructura/ Engineer. Foundations <br />may be cast In neat excavations provided written Footing <br />approval 15 obtolned and footings are Increased (- <br />2" in width. Use 2x12 plank at edge of excavation width III -I <br />to protect agolnst 5luffing, as required. III -I +211 I -I <br />6. A Geotechnical Engineer shall observe all footing <br />excavatlon5 prior to placement of reinforcing steel and <br />concrete. <br />5. Notify the 5tructura/ Engineer 4e hours before casting foundations. <br />Test and lnsnections <br />MI Washer <br />Steel Wa <br />;i Ito <br />I. Tests and Inspections -shall be provided as <br />required below and shall conform to the <br />requirements of 2001 GBG, Chapter 17A. <br />"(Px7ii6 " <br />3153 "x%6 it <br />76 11,P3 <br />2. All tests and inspections shall be performed by an <br />independent Inspection agency, <br />unless noted otherwise. Job5tte visits by the <br />5tructura/ <br />Engineer do not constitute <br />Inspections and are not a sub5tltute for Inpectlon. <br />20d 0.lg2Vx4" <br />3. It 15 the contractors sole responsibility to see that <br />these tests and Inspections are <br />performed. <br />noted <br />below or on plans shall be a minimum of two nails at each contact. <br />4. Tests. Required ® <br />IF <br />I. <br />5. Inspections <br />�] A. Fill compaction <br />® <br />A. <br />Footing excavation <br />® B. Concrete <br />or End Nall..............................2-16d <br />(by a Geotechnical Engineer) <br />® G. Sampling and Testing <br />2x6 k 2xe studs ................. TN each side .......................... <br />B. <br />Pile /pier Installation <br />OF Reinforcing Steel <br />Natl........... ................... <br />3-16d <br />C. <br />Reinforcement placement <br />D. Mill Certificates for <br />2-10d <br />or studs or End Nall..............................2-16d <br />Retnforcing Steel <br />W <br />D. <br />Concrete placement <br />E. Masonry <br />C <br />E. <br />Placing $ 5tres5ing tendons <br />® F. Grout (f Mortar <br />stuas .................................... ledger ................................... <br />2 -ed <br />F. <br />Rebar couplers <br />G. All complete penetration <br />5. <br />Double Top <br />groove welds by ultrasonic <br />® <br />6. <br />Masonry Placement $ grouting <br />testing or radiography <br />plate <br />lower late to 2x6 or 2x8...5,J...................................... <br />0 <br />H. <br />Shop welding <br />� H. Sampling f Testing of <br />1 <br />on typical detail sheet) <br />5tructura/ Steel <br />16. <br />0 <br />I. <br />Field welding <br />D 1. MIII Certificates for <br />= <br />J. <br />High strength bolting <br />5tructura/ 5teei <br />D <br />for widths more than 4':......................................16d <br />O <br />K. <br />Expansion or Epoxy anchors <br />J. Expansion or Epoxy <br />16d a 12'cc <br />staggered <br />anchors <br />L. <br />Shear stud Installation <br />Concrete Block Notes <br />1. Concrete block units shall conform to A5TM G -q0 grade N-1 light -weight units. <br />Compressive strength of units to be 1400 psi. Masonry prisms compressive strength <br />shall test not less than 1.25 times the speclFled Fm. 5peclfied f m=1.50apsl. <br />2. Mortar shatl be by volume: l part Portland cement; 4 to i part hydrated lime or <br />lime putty. and 2k2 to 3 times combined volume of cement and lime. 2" cubes shall test <br />1800 psi In 26 days. <br />3. Grout shall be by volume: I part Portland cement, 3 parts sand, �, part lime (optional). <br />2 parts pea gravel may be used where the least clear cell dimensions 15 4". Not more <br />than 536 of the pea gravel shall pass the No. 8 sieve and 10056 shall pass the -Ye� " <br />sieve. Grout shall test not less than 2000 psi In 28 days. <br />4. Retnforcing -steel shall conform to A5TM A615 -grade 60 for #4 and larger, grade 40 <br />For #3 and smaller. <br />5. Lap all bars 46 diameters, mtn)mum unless noted otherwise. <br />6. Before block Js placed on concrete, thoroughly clean concrete of all laltance and all <br />loose material. Roughen as In concrete constructlon joint. <br />7. Concrete block masonry shall be built to preserve the unobstructed vertical continuity <br />of the cells. Al! head end Joints shall be -solidly filled with mortar for a distance In <br />from the face of the wall or unit not less than the thickness of the longitudinal face <br />shells. Bond shall be provided by lapping 5ucce5slve courses or by equivalent <br />mechanical anchorage. <br />6. Vertical cells shall have vertical alignment sufficlent to mointoln a clear unobstructed <br />continuous vertical cell measuring not less than 2"x3". <br />q. Glean out openings shall be provided at the bottoms of all cells to be filled at each <br />lift or pour of grout where such lift or pour of grout Is In excess of 4'-O" In height. <br />Any overhanging mortar or other obstruction or debris shall be removed from inside <br />of such cells. The clean outs shall be sealed after inspection and before grouting. <br />Mechanically vibrate all rout ours. <br />l0. Vertical re nforcing shall be held In position at top and bottom and at intervals not to <br />exceed lq2 bar diameters. <br />IJ. Thoroughly clean all cells and bond beams of mortar before grouting. <br />12. All cells shall be filled solidly with grout. All grouting shall be done under the <br />continuous observation of a qualified Inspector where Indicated on plans. <br />13. When grouting is stopped for one hour or longer, horizontal constructlon joints Shall be <br />formed by stopping the pour of grout tom" below the top of the uppermost unit. <br />14. Each vertical bar In walls shall lap 48 diameters with a dowel of the same size <br />extending from the foundation. Garry each dowel to within 3" of the bottom of the <br />Foundation and terminate with 4/0° hook. Dowels shall be straight and plumb. <br />15. Place all horizontal bars in bond beam units. When 2 bars are used, stagger laps <br />minimum of 5'-O". <br />lb. Provide 2-#5 bars (full height of wall at Jamb and extending a minimum of 2'-0" past <br />edges of opening5 at head and sill) each side of all opening -5 and each end of all <br />walls, unless noted otherwise on drawings. <br />l7. All embedded Items (bolts, etc.) shall be secured In place prior to grouting. Provide a <br />minimum of P grout around all bolts In masonry. See Typical Details sheet. <br />l8. Use open end block for all stack bond construction. <br />19. Compliance with the requirements for the Specified compressive strength of masonry, <br />Fm shall be In accordance with 2001 CBC, section 2I05A.3.2 Masonry Prism Testing <br />I) A set of five Masonry Prisms shall be build and tested In accordance with UBC <br />accordance w/ UBC standard 21-17 prior to start of construction. <br />Materials used for the construction of the prism shall be taken from those <br />specified to be used In the project. Prlsm shall be constructed under the <br />observation of the special Inspector or approved agency and tested by an <br />opproved agency. <br />2)A set of three prlsm5 shall be built and tested during construction in <br />accordance w/ UBC standard 2l-17 for each 5000 square Feet of wall area, <br />but not less than three masonry prisms For the entire project. <br />3) Ful! allowable stresses were used In the design of the masonry walls. <br />4)Provide records of In5pectlon and certlfications on masonry to the owner, <br />architect $ engineer. <br />Note Iq <br />Plated blood Roof Truss Notes <br />Roof Design Loads <br />Top chord 11 psf DL <br />16 psf LL (reducible) <br />Bottom Chord 4 psf DL <br />l0 p5f LL (non -concurrent w/ top chord LL) <br />1. 2x6 minimum top chord typical - 2x4 all other members (U.N.O.). <br />2. All members shall be Douglas Fir (DF) No. 2 or better. <br />3. Truss drawings and calculations shall be submitted to the Architect and/or Engineer For <br />review prior to fabrication. Calculations for girder trusses shalt Include point loads <br />Prom carried truss reactions. All calculations shall be signed by a CIvII Engineer <br />registered in the State of Gallfornia. <br />4. Design and fabrication shall conform to the California Building Code (GBG), 2001 edition, <br />and TP/ -e5 of the Truss Plate institute. <br />5. Allowable stress Increase for load duration shall be /556 (percent) maximum. <br />6. Increase for allowable stre5-se5 for repetitive members, Section 4.3.4 of the N515 -4I <br />(National Design Specification) shall not be permissible. <br />7. Effects of eccentric loading shall be considered In the design of all jolnt5. <br />e. Truss manufacturer shall submit latest ICBG approved test data for truss metal plate <br />connectors to Architect and/or Engineer prior to fabrication. <br />4. Provide temporary erection bracing as required. <br />l0. General Contractor to provide web bracing as required by truss manufacturers design. <br />ll. Built-up girder trusses shall be laminated using % " bolts at 24 "cc maximum through all <br />members. <br />12. All hardware required for connecting trusses Jack to hip, hip to girder, girder to <br />girder, etc.) shall be designed, detailed and specified by truss fabricator. <br />13. General Contractor to verify all dimen-slons shown on tru-s5 profiles with Architectural <br />drawings and In field with wall layout prior to fabrication. Provide shop drawings with <br />dimensions reviewed and approved by General Contractor. <br />14. Tru55 manufacturer to provide plan drawing 5howing truss locations and truss profile <br />shop drawings prior to fabrication. <br />15. Truss manufacturer to account for the weight of all mechanical equipment In design of <br />all trusses which support such un1t5. See mechanical drawings for we/ght5 and detailing. <br />16. Wood under plates must be free of knots, knot holes and greatly distorted grains. <br />blood <br />1. All structural wood shall conform with the following specification: <br />Douglas Flr - Coast Region - WCLIB grading rules #l7 DF #1 except 2x4 and 2x6 wall <br />studs, plates, and blocking may be DF #2. <br />Redwood - Gallfornia Redwood Association 6rading Rules, latest edition. <br />Glued Laminated Beams - Standard Spec. for Structural Glued Laminated Timber RITC <br />ll7 latest edition. Submit shop drawings prior to fabrication of glued -laminated <br />members. Plywood - U.5. Product 5tondard PS. 2-92 for soft plywood 5truct I (I walls: <br />CDX ® floors and roof - U.N.O. <br />Pressure Treated Douglas Fir - 2001 GBG 5tondard No. 2303-3. <br />All wood shall have a moisture content of not more than I456 at time of construction. <br />2. All wood In direct contact with earth or concrete -shall be pressure treated. <br />3. Bearing and shear walls shall have double top plates, lapped at wall and partition <br />Intersection with 3-/6d nails. splice upper and lower plates 05 in Detall I on Typical <br />Detall sheet. <br />4. Provide solid blocking between Joists and rafters at all supports. <br />5. Provide blocking at all ceiling levels. <br />6. Joists under and parallel to partitions shall be doubled and nailed together. <br />7. Holes for bolts In wood shall be bored with a bit of the some, nominal diameter as the <br />bolt plus Ye" <br />8. Holes for lag screws shall be bored as follows: <br />a.) The clearance hole for the shank shall have the same diameter as the shank, <br />and the same depth of penetration as the length of unthreaded shank. <br />b.) The lead hole For the threaded portlon shall have a diameter equal to 60* to <br />7536 of the shank diameter and a length equal to at least the length of the <br />threaded portion. <br />c.) Lag screws and wood screws shall be screwed and not driven into place. Soap <br />may be used to lubricate the screws. <br />4. All bolts and lag screws shall be provided with metal washers under heads and nuts <br />which bear on wood. Applies also to inserted expanding Fasteners, Red Head, etc. <br />Bolt Diameter <br />MI Washer <br />Steel Wa <br />;i Ito <br />2 4 nOx X16 112�'rx2'LG <br />�sher <br />'X 4 It <br />i "(P3 <br />"(Px7ii6 " <br />3153 "x%6 it <br />76 11,P3 <br />"fix 16 a <br />3k2 nx3!'- " <br />1014, <br />4110xk2" <br />3� 1,X5%4rrx� is <br />1► <br />/0. All foundation sill bolts Shall use a minimum 2"x2"x%, plate washers. <br />ll. All bolts and lag screws shall be tightened on Installation and retlghtened before <br />closing in or of completion of Job. <br />12. Lay all structural plywood on roof and floors with face grain perpendicular to support <br />unless noted otherwise. <br />13. Block SPJolnts with 2x4 flat blocking where noted on roof or floor framing plans and <br />with blocking some as studs at walls. Use Qlycl/ps at mldsQan of unsupported Qlrywood <br />edges. <br />14. Connector hardware model number are those For 51mpson Strong-Tle Company. <br />Equivalent connectors with 16BO acceptance may be substituted. All Joist hangers <br />shall be 5lmpson U series unless noted otherwl5e. <br />15. Notify 5tructura/ Engineer after wall, floor, and roof 5P nailing has been completed <br />and a mtn)mum of 4e hours prior to concealing 5P. <br />chord bars <br />cont. thru <br />expansion J <br />typ., See <br />Naliln_a Schedule 5 <br />All halls for 5tructura/ work shall be common wire nails conforming to the following minlmUm 51Z,96.. <br />ec tions <br />�4.12 <br />max. _ 2 `-O" <br />U.n.O. <br />A1B <br />2-#5 vert full -ht <br />c� �� mintclp. see plans for <br />\ spec7ol Jamb bar req't5 <br />/ dowels <br />5ectlon A fnd. typ <br />" clr <br />ylo �2-#5 <br />add'i full -ht <br />/Intel a vert. typ <br />lection B corners f <br />Inter -sections <br />��_ �5 (#5 min.) <br />-- �"-- -Jamb bars run full <br />height of cont. b/k. <br />2-#5 bars top f bottom wall ea. side of <br />OF all opening5 opng typ. provide- <br />dowel <br />rovidedowel ® Ptg <br />klall O,c�eni�geinfor�inc� <br />m <br />lap <br />46D <br />corner bor-s moy - <br />be used In lieu of <br />single bend typ. <br />t2-#5 min. <br />Full ht. vert5. <br />see plan For <br />special bar <br />req'ts. <br />Notes: ` `- <br />l. Concrete block shall be placed in running bond U.N.O. <br />2. 51ze and spacing of reinforcing is shown elsewhere on drawings. <br />�i TuaiGal Blo6k Nall Gomer and <br />.4:12 lnterSeG tion �e in>corc inq <br />ni <br />-1 <br />0 <br />o � <br />backer rod 8 0 <br />caulking full -ht. k <br />ea. side w o <br />I X <br />#5 Full -ht. vert. ea. - <br />side of expon5lon _ ft <br />cmu wall <br />expansion Joint <br />® 32'-O"cc max. <br />Ora,-:, shown on <br />plans <br />around bolt typ <br />8d 0.131 "Ox2�" <br />J <br />0 <br />lad 0.148"Ox3" <br />grout <br />10d shorts 0.148"-Dxl-"plus thlckne56 of S.P. <br />bolt <br />z <br />16d 0.162" (Px3� " <br />�\ <br />20d 0.lg2Vx4" <br />t. <br />Holes shall be Sub -drilled where necessary to prevent splitting. Nalling not <br />o <br />noted <br />below or on plans shall be a minimum of two nails at each contact. <br />8d nails for I " material and 16d nall5 For 2" material. <br />IF <br />I. <br />Joists or Rafter5........... at all bearings ..................... TN each side .......................... <br />2 -lad <br />2. <br />Studs to Bearings. ......... <br />2x4 studs ................................ TN each side ..........................2-10d <br />or End Nall..............................2-16d <br />2x6 k 2xe studs ................. TN each side .......................... <br />3 -lad <br />Natl........... ................... <br />3-16d <br />3. <br />Blocking .............................. <br />orEnd <br />between Jol5t5, rafters,......... each side, each end .... <br />2-10d <br />or studs or End Nall..............................2-16d <br />between folst or rafter.......... TN each side ..........................3-!Od <br />bearing (plates) <br />4. <br />Ledger.................................to <br />stuas .................................... ledger ................................... <br />2 -ed <br />2" ledger..................................2-16d <br />5. <br />Double Top <br />Plates...................................lower <br />to 2x4 stud........................................................ .2-16d <br />plate <br />lower late to 2x6 or 2x8...5,J...................................... <br />.3-16d <br />1 <br />1 <br />upper plate to lower plate ... (5ee typical framing detail <br />1 <br />on typical detail sheet) <br />16. <br />5111 P/ates ..........................to <br />parallel framing................................................................... <br />20d a 12"cc <br />1 <br />1 <br />to perpendicular framing....... each contact...................2-20d <br />7. <br />Multiple 5tud5...................stagger <br />for widths more than 4':......................................16d <br />® 12 "cc <br />6. <br />Built Up Beams ................ <br />10" or less In depth each side ......................................... <br />16d a 12'cc <br />staggered <br />more than l0" In depth ........................................................ <br />� ",P bolts at <br />24"cc staggg'Bred <br />4. <br />Ceiling 5trlpping.............holes <br />shall be predrllled................... 1 thick .......... .........2-8d <br />(1 -slant) <br />2" thick ................... <br />2-16d (I -slant) <br />ends of strJpping boards <br />where ceiling Is plaster or A 11gypsum <br />use Annular Ring Nails (no slant) <br />lO. <br />Structural <br />Plywood..........................................................................................................................................5ee <br />Typical <br />Detall Sheet <br />/!. <br />Non -Structural <br />Plywood...............................at <br />supported edges ......................... flnl5h nails .................. <br />6d ® 6 "cc <br />at interior bearings..........................finish nolls..................6d <br />® 6 "cc <br />ec tions <br />�4.12 <br />max. _ 2 `-O" <br />U.n.O. <br />A1B <br />2-#5 vert full -ht <br />c� �� mintclp. see plans for <br />\ spec7ol Jamb bar req't5 <br />/ dowels <br />5ectlon A fnd. typ <br />" clr <br />ylo �2-#5 <br />add'i full -ht <br />/Intel a vert. typ <br />lection B corners f <br />Inter -sections <br />��_ �5 (#5 min.) <br />-- �"-- -Jamb bars run full <br />height of cont. b/k. <br />2-#5 bars top f bottom wall ea. side of <br />OF all opening5 opng typ. provide- <br />dowel <br />rovidedowel ® Ptg <br />klall O,c�eni�geinfor�inc� <br />m <br />lap <br />46D <br />corner bor-s moy - <br />be used In lieu of <br />single bend typ. <br />t2-#5 min. <br />Full ht. vert5. <br />see plan For <br />special bar <br />req'ts. <br />Notes: ` `- <br />l. Concrete block shall be placed in running bond U.N.O. <br />2. 51ze and spacing of reinforcing is shown elsewhere on drawings. <br />�i TuaiGal Blo6k Nall Gomer and <br />.4:12 lnterSeG tion �e in>corc inq <br />ni <br />-1 <br />0 <br />o � <br />backer rod 8 0 <br />caulking full -ht. k <br />ea. side w o <br />I X <br />#5 Full -ht. vert. ea. - <br />side of expon5lon _ ft <br />cmu wall <br />expansion Joint <br />® 32'-O"cc max. <br />Ora,-:, shown on <br />plans <br />around bolt typ <br />J <br />0 <br />c <br />grout <br />y�. <br />bolt <br />z <br />UCTURAL <br />�\ <br />w <br />t. <br />0o� <br />o <br />wz <br />-16o <br />L <br />IF <br />1. Do not splice chord bars within 4'-0" of expansion Joint. <br />2. Expansion JoJnt5 shall not occur within 4'-0" of window or <br />door openings. <br />Typical Blo6k Nall Fxban510n Joint <br />45° <br />q0°� 4d 2k" min. <br />/V <br />Tunical f-fook5 � Bends <br />40° <br />Z <br />d = Rebar diameter <br />D= bd for #3 thru #8 <br />\0� D= 8d for #q thru #ll <br />Ties 5tirruo-c? D= lad for #14 thru #18 <br />� Rebar HOok3 Benal5 <br />4.12i <br />SCALE <br />DESIGNED BY <br />DRAWN BY <br />CHECKED BY <br />RECORD DWGS. <br />I" l" min. clr. all <br />Notes: <br />1. Bolt cast In masonry shall be grouted In place wlth I " min. of <br />grout between bolt and masonry. <br />2. Use temporary plywood stop to retain grout as required. <br />Tur iG <br />a/ Bolt G a5 t in %las onr <br />see typ conc notes <br />or wall elevations <br />For lamb bars <br />i <br />O <br />2-#5 min. <br />Dowe/s From --i <br />below <br />T o l6 a l Jamb Re in f arc in <br />\4.12 <br />MUNICIPAL UTILITIES DEPARTMENT <br />CITY OF STOCKTON, CALIFORNIA <br />APPROVED BY. S"! 4-0E <br />DATE <br />ASSISTANT DIRECTOR <br />ESS <br />around bolt typ <br />J <br />0 <br />c <br />grout <br />y�. <br />bolt <br />z <br />UCTURAL <br />�\ <br />w <br />N <br />ON <br />0o� <br />o <br />wz <br />-16o <br />Notes: <br />1. Bolt cast In masonry shall be grouted In place wlth I " min. of <br />grout between bolt and masonry. <br />2. Use temporary plywood stop to retain grout as required. <br />Tur iG <br />a/ Bolt G a5 t in %las onr <br />see typ conc notes <br />or wall elevations <br />For lamb bars <br />i <br />O <br />2-#5 min. <br />Dowe/s From --i <br />below <br />T o l6 a l Jamb Re in f arc in <br />\4.12 <br />MUNICIPAL UTILITIES DEPARTMENT <br />CITY OF STOCKTON, CALIFORNIA <br />APPROVED BY. S"! 4-0E <br />DATE <br />ASSISTANT DIRECTOR <br />ESS <br />SHEET NO. William D. Bevier <br />Structural Engineer, Inc. <br />SHEETS 2479 Sunrise Blvd. <br />Gold River, CA 95670 <br />BE VIER Telephone (916) 631-3030 <br />►nn intim am STRUCTURAL ENGINEERING Facsimile (916) 631-8996 <br />WILLIAM <br />a <br />0 <br />c <br />N 71I <br />0 <br />o <br />1 /07 <br />))� <br />z <br />UCTURAL <br />�\ <br />SHEET NO. William D. Bevier <br />Structural Engineer, Inc. <br />SHEETS 2479 Sunrise Blvd. <br />Gold River, CA 95670 <br />BE VIER Telephone (916) 631-3030 <br />►nn intim am STRUCTURAL ENGINEERING Facsimile (916) 631-8996 <br />1 <br />I <br />a <br />0 <br />JZ <br />_l <br />0 <br />o <br />4 <br />i ca) <br />z <br />z � � <br />cNMQONi <br />w <br />N <br />ON <br />0o� <br />o <br />wz <br />-16o <br />L <br />1 <br />O <br />O <br />U <br />c <br />Q Q <br />J <br />(L Z <br />Z W <br />W <br />2 W <br />j J <br />O Lit <br />cc <br />2 <br />cc <br />W Z <br />W <br />LL LL= <br />O <br />Q <br />Z <br />I <br />J <br />W <br />J <br />W N <br />W T 0 <br />I <br />0 <br />Q <br />V) <br />LL <br />O <br />H <br />V <br />O <br />le <br />0 <br />co <br />N <br />0) <br />N N t0 <br />0 <br />< <br />0 <br />o <br />■■ <br />wQ O N <br />Z <br />a!'1M <br />z � � <br />cNMQONi <br />� <br />N <br />ON <br />N <br />ho M <br />wz <br />-16o <br />L <br />0- <br />O <br />O <br />U <br />c <br />Q Q <br />J <br />(L Z <br />Z W <br />W <br />2 W <br />j J <br />O Lit <br />cc <br />2 <br />cc <br />W Z <br />W <br />LL LL= <br />O <br />Q <br />Z <br />I <br />J <br />W <br />J <br />W N <br />W T 0 <br />I <br />0 <br />Q <br />V) <br />LL <br />O <br />H <br />V <br />O <br />le <br />0 <br />co <br />