Laserfiche WebLink
FINISHED GRADE 6.. ADJUST BOX TO GRADE <br /> PER CITY STANDARD <br /> PLAN 114 <br /> ° • 9„ . e <br /> CONCRETE COLLAR <br /> •• N (NOT REQUIRED IN <br /> SIDEWALK AREA) <br /> 'v <br /> CONCRE CONCRE E <br /> BASE BASE 6" <br /> z <br /> 2 8"PVC(C900) <br /> (ONE SOLID <br /> PIECE) <br /> BLACK 10 MIL TAPE <br /> MIN 8" (POLYWRAP)(TYP.) <br /> DUCTILE IRON PIPE <br /> 6"SAND BEDDING <br /> FLG X FLG or <br /> I FLG X MJ /\ \��\��\�/i. <br /> NOTES : <br /> 1. VALVES SHALL BE ONE OF THE FOLLOWING: <br /> A)BUTTERFLY VALVES:12"AND LARGER AS SHOWN ON APPROVED MATERIALS LIST SHALL BE USED. <br /> APPROVED LIST INCLUDE:("GROUNDHOG"), ("AMERICAN"),MUELLER,B.I.F.,KENNEDY,DRESSER. <br /> B)GATE VALVES: 10"AND SMALLER AS SHOWN ON LIST OF APPROVED MATERIALS.APPROVED LIST <br /> INCLUDES:MUELLER RESILIENT SEAT,CLOW R/W,KENNDEY,AMERICAN-80"CRS". <br /> 2. OPERATING NUTS SHALL BE RAISED TO WITHIN 4'OF FINISHED STREET GRADE WITH REQUIRED <br /> EXTENSIONS BEING PROVIDED BY VALVE MANUFACTURER. <br /> 3. POLYWRAP ALL PIPES AND VALVES. <br /> 4. VALVES SHALL BE TESTED BY MANUFACTURER AS FOLLOWS:6"-12",175 PSI;14"AND LARGER, <br /> 150 PSI. IN ADDITION,HYDROSTATIC TESTS AGAINST FULLY CLOSED VALVE VANES SHALL BE DONE AS <br /> FOLLOWS: 6"-12", 350 PSI; 14"AND LARGER,300 PSI. <br /> 5. VALVE BOX: BROOKS 3-RT OR CHRISTY G5 WITH G5C LID. <br /> CITY OF rPRACY <br /> r REVIEWED BY: Vg <br /> STANDARD <br /> ® PLAN 402 <br /> CITY ENGINEER RCE 37186 No. <br /> TRACY Res No. 2008-255 DATE: <br /> V. ' F VALVE, BOX & <br /> � Rev: Rev: <br /> RISER <br /> Think Inside the Triangle'" Rev: Rev: <br />