Laserfiche WebLink
PROJECT DETAILS <br />RULE 16 UPGRADE TX AND INSTALL OH SERVICE FOR 200A 1Ø RESIDENTIAL <br />APPLICANT INSTRUCTIONS <br />LOC 2:INSTALL CUST OWNED POLE AND 200A SERVICE PANEL <br />PG&E ELECTRIC CREW INSTRUCTIONS <br />LOC 1: REPLACE 25kVA TX WITH 50kVA TX <br />REMOVE 8' SECONDARY ARM <br />INSTALL 8' COMPOSITE SECONDARY ARM, LOWER AS NEEDED TO MEET CLEARANCES <br />LOWER 5/16" GUY ATTACHMENT TO BELOW SECONDARY ARM <br />REPLACE 6 DPX SECONDARY WITH 4/0A TPX (55') <br />INSTALL WOOD STEP ABOVE COMM LINES <br />LOC 2: INSTALL 4/0A TPX SERVICE (40') <br />MAKE CONNECTIONS AND SET 200A 1Ø METER