Laserfiche WebLink
AFFORDA-1 )T <br /> 4162 d street Galt, Ca. 95632 AST TANK TEST <br /> 209 744-0112 Fax 209 744-0116 PRIMARY & A ,%,4R- '----,, <br /> Site: DEPT. OF CORRECTIONS DVI Test Date: 08/02/2010 DEC 2 4 e-u Iu <br /> Address: 23500 KASSON ROAD <br /> City: TRACY, CA 95304 Equipment: GAUGE & NITROCI'WIRONMENTALHEALTH <br /> PEMAITISERVtM <br /> Test Method Developed By: Tank Manufacturer Industry Standard X Professional Engineer <br /> Other(Specify): <br /> Test Method Uses: Pressure X Vacuum Hydrostatic <br /> Other(Specify): <br /> Measuring Equipment Used for"Testing:2 %"Gage&Nitrogen <br /> Tank# I Tank# I Tank# Tank# <br /> ® PRIMARY ❑ PRIMARY ❑ PRIMARY ❑ PRIMARY <br /> ❑ ANNULAR ® ANNULAR ❑ ANNULAR ❑ ANNULAR <br /> 2000 2000 <br /> Tank Capacity: <br /> STEEL STEEL <br /> Tank Material: <br /> EMPTY DIESEL EMPTY DIESEL <br /> Product Stored: <br /> Wait time between applying <br /> Pressure/vacuum/water and starting 5 MIN 5 MIN <br /> test: <br /> 1115 1145 <br /> Test Start Time. <br /> 3.5 PSI 3.1 PSI <br /> Initial Reading(Ri): <br /> 1245 1245 <br /> Test End Time: <br /> 3.5 3.1 <br /> Final Reading(Rt): <br /> 1 HR IHR <br /> Test Duration: <br /> 0 0 <br /> Chane in Reading(Rf-Ri): <br /> 0 +/- 0 +/- <br /> Pass/Fail Threshold: <br /> PASS PASS <br /> Test Result: <br /> NO SENSOR NO SENSOR <br /> Was sensor removed for testing? <br /> Was sensor properly replaced after <br /> testing? NO SENSOR NO SENSOR <br /> Technician: LDY}L�EE NIMMO Date: 8/2/10 <br /> Signature: �v OTTL:#90-1143 EX.: 12-31-12 ICC:#5249115UT EX:6-30-11 <br /> Comments: The sensors and probe were not installed. <br />