Laserfiche WebLink
• API 653 In-Service Inspection Report m m hb� <br /> for mm mm m <br /> Pacific Ethanol HMT Inspection <br /> Tank No. T-6102 August 6,2013 <br /> Stockton, CA Page 33 of 46 <br /> TABLE C <br /> FIXED ROOF READINGS <br /> (in inches) <br /> PLATE NO. Reading Reading Reading <br /> 7 2 3 <br /> 1 0.315 0.316 0.313 <br /> 2 0.315 0.318 0.316 <br /> 3 0.312 0.312 0.312 <br /> 4 0.316 0.316 0.319 <br /> 5 0.312 0.311 0.309 <br /> 6 0.310 0.312 0.313 <br /> 7 0.318 0.318 0.318 <br /> 8 0.320 0.319 0.319 <br /> MIN.: 0.309 AVG.: 0.315 <br /> RECEIVED <br /> • AUG 14 2014 <br /> APIRPTNE.DOT REV 2 23262666R8102r(Rev 1) 11/620131:10 PM <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br />