Laserfiche WebLink
• API 653 In-Service Inspection Report MM h�A� <br /> for mmmm W <br /> Pacific Ethanol HMT Inspection <br /> Tank No. T-6103 August 7,2013 <br /> Stockton, CA Page 7 of 46 <br /> SUMMARY AND REPAIR RECOMMENDATIONS (CONT'D.) <br /> FIXED ROOF: <br /> Visual (VT) inspection and Ultrasonic (UT) testing was performed in accessible <br /> locations. <br /> Visual (VT) inspection noted the entire roof and handrail coating is weathered and is <br /> showing signs of chalking. The coating is intact with no areas of failure that expose the <br /> underlying carbon steel. There is product residue on the roof plates. Consideration <br /> should be given to properly cleaning the product residue and monitoring the coating <br /> integrity. <br /> Nominal thickness of the roof is 0.312 inch and the lowest thickness obtained during this <br /> inspection was 0.313 inch. <br /> • <br /> RECEIVED <br /> AUG 149n14 <br /> APIRPTNE.DOT REV 2 23262888RE1 par(Rev 1) 10131:30 PM <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br />