Laserfiche WebLink
• API 653 In-Service Inspection Report <br /> for m m m m M <br /> Pacific Ethanol HMT Inspection <br /> Tank No. T-6103 August 7,2013 <br /> Stockton, CA Page 25 of 46 <br /> 5.4 NOZZLE INSPECTION <br /> External shell nozzle welds were inspected utilizing VT inspection methods. <br /> Shell and roof nozzle UT data was collected utilizing random readings. One reading per <br /> nozzle neck, reinforcing pad, flange face, and cover (when applicable) was taken. (ref. <br /> Sections 4.4.2 and 4.5.2). <br /> 5.5 FIXED ROOF INSPECTION <br /> External fixed roof plates were inspected utilizing VT inspection method. <br /> Fixed roof deck plate UT data was collected utilizing random readings. Three (3) <br /> readings per plate were taken (ref. Table C). There were no readings which exceeded <br /> 0.090 inch or less (ref. API 653, 4.2.1.2). <br /> • <br /> RE EN EU <br /> AUG 14 2014 <br /> APIRPTNE.DOT REV 2 23262666?8103r(Rev 1) 1116120131'30 PM <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br />