• API 653 In-Service Inspection Report Min <br /> for <br /> Pacific Ethanol HMT Inspection <br /> Tank No. T-6101 August 6,2013 <br /> Stockton, CA Page 23 of 44 <br /> 4.5.2 FIXED ROOF NOZZLE TABLE <br /> Pipe Neck <br /> Size Location Thick <br /> Item Description in. Plate No. in. Comments <br /> A Nozzle 3.0 1 0.222 Automatic Tape Guide <br /> B Nozzle 3.0 4/ 3 0.209 Tank Radar <br /> C Coupling 2.0 4/3 --- Level Alarm <br /> D Nozzle 12.0 3/5 0.362 Free Vent <br /> E Coupling 2.0 3/6 --- Level Alarm <br /> F Manway 36.0 7 0.258 --- <br /> RECEIVED <br /> AUG 14 2014 <br /> APIRPTNE.DOT REV 2 2326286arr-61011(2) 101212013 8'10 AM <br /> ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br />