Laserfiche WebLink
SWRCB, January 2002 <br />6. PIPING SUMP TESTING <br />Page of <br />Test Method Developed By: ❑ Sump Manufacturer ❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure F Vacuum X Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />Sump # 1 <br />Sump # <br />Sump # <br />Sump # <br />Sump Diameter: 36" <br />Sump Depth: 13''/2" <br />Sump Material: Fiberglass <br />Height from Tank Top to Top of 10" <br />Highest Piping Penetration: <br />Height from Tank Top to Lowest 12" <br />Electrical Penetration: <br />Condition of sump prior to testing: Dry <br />Portion of Sump Tested' Water Level 13" <br />Does turbine shut down when <br />sump sensor detects liquid (both N/A Suction System <br />product and water)?* <br />Turbine shutdown response time N/A <br />Is system programmed for fail-safe N/A <br />shutdown?* <br />Was fail-safe verified to be N/A <br />operational?* <br />Wait time between applying water <br />5 Minutes <br />and starting test: <br />Test Start Time: 1:05 <br />Initial Reading (Ri): .001 <br />Test End Time: 1:35 <br />Final Reading (RF): .001 <br />Test Duration: 30 Minutes <br />Change in Reading (RF -RI): 0 <br />Pass/Fail Threshold or Criteria: .005/30 Minutes <br />Test Result: Pass <br />Was sensor removed for testing? Yes <br />Was sensor properly replaced and Yes <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Suction System. <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to ny of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />