Laserfiche WebLink
AFFORDA-TEs,r AST TANK TEST <br /> 4162 d Street Galt,Ca. 95632 <br /> 209 744-0112 Fax 209 744-0116 PRIMARY & ANNULAR <br /> Site: DART CONTAINER Test Date: 1/13/2011 <br /> Address: 1400 E. VICTOR RD. <br /> City: LODI, CA 95240 Equipment: PSI GAUGE <br /> Test Method Developed By: Tank Manufacturer Industry Standard XXX Professional Engineer <br /> Other(Specify): <br /> Test Method Uses: Pressure XXX Vacuum Hydrostatic <br /> Other(Specify): <br /> Measuring Equipment Used for Testing:PSI GAUGE <br /> Tank# 1 Tank# Tank# Tank# <br /> ® PRIMARY ❑ PRIMARY ❑ PRIMARY ❑ PRIMARY <br /> ❑ ANNULAR ❑ ANNULAR ❑ ANNULAR ❑ ANNULAR <br /> Tank Capacity: 10,038 <br /> STEEL <br /> Tank Material: <br /> DIESEL <br /> Product Stored: <br /> Wait time between applying <br /> Pressure/vacuum/water and starting SET UP TIME <br /> test: <br /> 1412 <br /> Test Start Time: <br /> 3.00 <br /> Initial Reading Ri): <br /> 1512 <br /> Test End Time: <br /> 3.00 <br /> Final Reading(RO: <br /> Test Duration: HR <br /> 0 <br /> Change in Reading Rf-Ri): <br /> 0 <br /> Pass/Fail Threshold: <br /> PASS <br /> Test Result: <br /> NONE <br /> Was sensor removed for testing? <br /> Was sensor properly replaced after <br /> testing? N/A <br /> Comments Technician: ZANE NIMMO <br /> OTTL#04-1676 ICC 5263322-UT ICC 5263322-U3 <br /> Oregon UST Service#26755 Oregon UST Tank Tightness#26756 <br /> Nevada UT-2206 <br /> Signature: <br /> Date: 1/13/11 <br /> C- - ,� <br />