<br /> .� \//V�� .n: Inspect li,r signs ofconosion around X111
<br /> I,Iliilllltil ;lllii „t,,,,,C•„t,• (�l; .ri,,;,,}_ was noted on the I 1>i rl ^ O
<br /> Itreonnnrn�iatiorls Kciurnrncn,i prepping and rl+acing,Ihr I I 1 c,t luanv.a}
<br /> �
<br /> (D
<br /> (n
<br /> iUtTOSloll.
<br /> V
<br /> (n I I•ENI 7: COND cone: 5
<br /> Scrtion 3.2.1.1 B -- SHELL MANWAY "S
<br /> e--F� Line item 3.2.1.1.a: Inspect for signs of corrosion around all nozzles.
<br /> (n Condition and comments: Minor pitting Nvas noted on the 1.1)of manway "O” -'
<br /> Recommendations: Recommend prepping and coating the 1. of manway "O” to mitigate"f( —•
<br /> corrosion.
<br /> =7 ITEM 8: GOND CODE: 5
<br /> Section 3.2.1.113--SHELL MANWAY
<br /> 1-3 Line item 3.2.1.Le: Additional inflormation•?
<br /> Condition and comments: No tale tell hole is currently installed on the repad for mama ay "O".
<br /> 0 Recommendations. Recommend installing a .2501" tale tell hole to this repad, then soapy water and N
<br /> pressure test the Fepad for leaks.
<br /> cD 0
<br /> N ITEM 9: COND COBE- 5 0
<br /> o
<br /> -'' Section 3.2.1.2 --THERIVivOWELL NOZZLE
<br /> rNv Line item 3.2.1.2.e: Inspect for signs of corrosion or other defects around the nozzle.
<br /> Cpadilion and comments: Thermo well nozzles "K" and 1 t." are of the threaded connection t
<br /> Q RecoIu=endatlons: Recommend replacing with flange type nozzle to eliminate threaded conn-
<br /> on the tank.
<br /> 0• ITEM 10: COND CODE: 5 (n
<br /> Section 3.2.1.9-- INLET SHELL RELIEF NOZZLE
<br /> Line item 3.2.1.9.8: If threaded, is it seal welded'? —
<br /> Condition and comments: Threaded connection is not seal welded.
<br /> Recommendations: Recommend replacing threaded connection with a nange type ttozale tO
<br /> r
<br /> oeliminate threaded connections on tank. r O
<br /> o ITEM 11: COND CODE: 5 ,
<br /> Section 3.2.1.10 --OUTLET SHELL Rl.,AAF,F NOZZLE
<br /> m ine item 3.2.LI O.f. Is the piping fastened with welded or threaded fittings?" e--f
<br /> 0 ondition and comments: Threaded connewton is not seal welded.
<br /> C_ ecommendations: Recommend replacing tl ceoded connection with a flange type no to (n
<br /> liminate threaded connections on tank. O
<br /> v C7
<br /> 0
<br /> G) AI 1,,mill -1 OF 157