Laserfiche WebLink
5.0 Extemal Shell <br />External Coatings <br />Tank External Coating <br />•.Comments/Recommendations <br />Paint <br />External Coating Condition <br />Fair <br />Tank has paint failure and corrosion around welds on <br />end caps and roof. <br />Other <br />Shell <br />Condition Of Welds <br />•♦:Comments/Recommendations <br />Good <br />Corrosion <br />Yes <br />Around welds and roof of tank. <br />Evidence of Distortion <br />No <br />Mechanical Damage <br />No <br />Evidence of Leaks <br />No <br />Repads or Changes to Original Design? <br />lNo <br />Other <br />ati on <br />Insulation Missing? <br />•.Comments/Recommendabons <br />N/A <br />Evidence of Moisture? <br />N/A <br />Evidence of Mold? <br />N/A <br />Damage to Insulation? <br />N/A <br />Corrosion Under Insulation? <br />N/A <br />Other <br />Tank Roof <br />Standing Water(low areas)? <br />Observations <br />No <br />Comments/Recommen'dations <br />Coating Failure? <br />Yes <br />Other <br />The tank is equipped with spill control and/or CRDM (continuous release detection method <br />and is considered a Category 1 tank per table 5.5 of STI SP001. The next formal inspection <br />would be required in 20 years or as required by the sites SPCC Plan. The inspection <br />ormal Inspection Is Required in (years): schedule is based on the site completing the recommended repairs as noted in the <br />inspection report. If problems are identified during periodic inspections a formal inspection <br />may required soon. The condition of the equipment may change after the issuance of this <br />report. <br />)ther <br />