Laserfiche WebLink
Inspection Summary <br />An STI SP001 formal external inspection that included visual examination was conducted. The inspection was completed on <br />12/5/2017. The tank is located at Tracy Municipal Airport, 5749 Tracy Blvd. in Tracy, CA. The following is a detailed report of the <br />inspection including findings and recommendations. <br />1.0 GenerallTank Information <br />General Information <br />•.Comments/Recommendations <br />Facility Name <br />Tracy Municipal Airport <br />Facility ID <br />AIRPORT <br />Compliance Records Available? <br />N/A <br />Tanknolo y Work Order No. <br />6702244 <br />Other <br />N/A <br />Tank Data <br />•.Comments/Recommendations <br />ank Nameplate <br />Underwriters Laboratories Inc <br />ank Name / Number <br />2 <br />Tank Layout (Horizontal, Vertical, other) <br />Horizontal <br />Tank Design (Single wall, double wall, other) Double Wall <br />ank Construction Material (carbon, <br />Carbon Steel <br />This is a Compartmentalized double wall Tank. <br />stainless, other) <br />Tank size (nominal gallons) <br />15882 <br />Tank Shape <br />Cylinder <br />Tank Length <br />408 inches <br />Tank width / diameter / circumference <br />107 inches <br />Tank Height <br />113 inches <br />Tank Contents <br />AVGAS100 <br />8000 Gallons per compartment <br />Cathodic Protection <br />None <br />Continuous Release Detection Method <br />Elevated /Visual <br />(CRDM) <br />Release Prevention Barrier (RPB) <br />Double Wall <br />Spill Control <br />Concrete Pad <br />Other <br />N/A <br />Foundations And Supports <br />Observations <br />Comments/Recommendations <br />Tank Foundation Type <br />Concrete Pad <br />Tank Foundation Condition <br />Good <br />Tank Support Type <br />Steel Legs <br />Tank supports have paint failure and corrosion, <br />Tank Support Condition <br />Fair <br />Recommend cleaning and painting to prevent further <br />ama e. "' <br />ank Protection (bollards, fence, other) <br />IFence <br />Fence is in good condition <br />Other <br />N/A <br />Signage As Required By NFPA i <br />•.Comments/Recommendations <br />Filling Procedures Posted At Fill As <br />Yes <br />Required? <br />"No Smoking" Signage Present As Required? <br />Yes <br />Emergency Contact Numbers Posted As <br />No <br />Emergency plan is required and should include posting <br />Required? <br />of emergency contact numbers. <br />Tank Capacity And Tank ID Posted On The <br />Yes <br />Tank As Required? <br />NFPA Signage - On The Tank, At Facility <br />Entrance, And As Designated By Fire Code <br />Official. Labels Include Contents And NFPA <br />es <br />704 Diamond Hazard Signs. <br />Other <br />N/A <br />