Laserfiche WebLink
Central Petroleum MaintenNce (925) 462-4060 <br /> 176 Wyoming Street, P.O. Box 211 FAX (925) 462-8352 <br /> Pleasanton, CA 94566 <br /> VAPORLESS MANUFACTURING, INC. <br /> LDT-S90 Leak Detector Test Record <br /> Customer Date <br /> CHEVRON 2-4-09 <br /> Address City TRACY <br /> 3400 MAC ARTHUR <br /> Technician Product <br /> GREGG GELTZ 87 <br /> Submersible Pump Identification <br /> Manufacturer Model No. Serial Number <br /> FE PETRO <br /> Manufacturer Leak Detector Identification <br /> Description Other Style Leak Detector <br /> VAPORLESS - LD-99#2000 <br /> Diaphram-Type <br /> Piston Type X <br /> Tamper-proof seal installed? Yes No X <br /> Leak Detector in Submersible Pump <br /> Test At Dispenser <br /> Retest <br /> 1. Operating Pump Pressure 30 psi (para.15) 1 psi (para.15) <br /> 2. Gallons per hour rate 3.0 (para.22) 2 (para. 22) <br /> 3.Line Pressure with pump shut off. 26 psi (para.25) 3.___ psi <br /> 4. Bleedback Test with pump off 400 ml (para.26) 4. ml (para.26) <br /> 5. Step-through time to full flow 2-3 seconds(para. 30) 5. seconds (para. 30) <br /> 6. Leak detector stays in leak search position (para. 42) Yes: X 6. Yes: <br /> No: No: <br /> 7. Leak Detector Test: Pass: X 7. Pass' <br /> Fail: Fail <br /> Note.Pass=Leak Detector fits lest protocal <br /> Failed=Leak Detector fails test protocal <br /> 8. Leak Detector Replaced Yes: 8. Yes: <br /> No: X <br /> No: <br /> SUB - PUMP APPROXIMATE OPERATING PRESSURE <br /> Red Jacket 3/4 HP 28 PSI <br /> Red Jacket 1 1/2 HP 30 PSI <br /> Red Jacket X3 1 1/2 HP 43 PSI <br /> FE Petro 1 1/2 HP 30 PSI <br />