Laserfiche WebLink
1400 RF(%,Fl <br /> D <br /> LDT 5000 Field Test Apparatus APAgO I DZ01 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2317099 Date: 2/21/2014 ENVIRONME AL <br /> HEALTH DEPAMM <br /> Site Name/ID: TRACY PETRO/Tracy Petro <br /> Address: 3400 N. MACARTHUR DR <br /> City: TRACY State: CA Zip: 95376 <br /> ank ID T3 Ti T1 T2 T2 <br /> roduct Diesel PREMIUM PREMIUM REGULAR REGULAR <br /> roduct Line <br /> rested From 1 1 1 1 1 <br /> xisting/New Existing Existing Replacement Existing Replacement <br /> echanical/Electronic Mechanical Mechanical Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-200C Vaporless LO-2000 Vaporless LD-200C Vaporless 1-0-200 Vaporless LD-200 <br /> erial No. 03120005 10051164 14014-1402 06101129 1401-1407 <br /> ump Operating Pressure(psi) 35.00 35.00 38.00 50.00 45.00 <br /> alibrated Leak(ml/min) 189.0 189.0 189.0 189.0 189.0 <br /> alibrated Leak(gph) 3.00 3.00 3.00 3.00 3.00 <br /> olding PSI 33.00 35.00 35.00 50.00 45.00 <br /> NIA for Electronic LD's <br /> esiliency(ml) 150.00 204.00 250.00 1600.00 1000.00 <br /> NIA for Electronic Lo's <br /> Metering PSI 19 0 21 0 25 <br /> NIA for Electronic Lo's <br /> pening Time(sec) 2 0 2 0- 35 <br /> NIA for Electronic LD's <br /> est Results Pass Fail Pass Fail Pass <br /> Technician Comments: <br /> Technician Name: Brent Bowen Certification#: 99937 <br /> Technician Signature: Expire Date: 7/28/2016 <br /> Environmental Compliance for Petroleum Systems <br /> ©2014 Tankndm Inc.,Aw r,Tx. All iiphls resenetl. IeNmdop.. <br />