Laserfiche WebLink
Emergency Vent Manufacturer-Primary Tank N/A <br /> Emergency Vent Size-Primary Tank 21" <br /> Emergency Vent Model-Primary Tank Long Bolt Manway <br /> Does the Emergency Vent Operate As <br /> Designed? es <br /> Is the Emergency Vent Properly Sized? Yes <br /> Emergency Vent Manufacturer-Secondary Morrison Brothers <br /> Tank <br /> Emergency Vent Size-Secondary Tank 8" <br /> Emergency Vent Model-Secondary Tank 244 <br /> Does the Emergency Vent Operate As <br /> No Vent is frozen, unable to unfreeze vent. <br /> Designed? <br /> Is the Emergency Vent Properly Sized? Yes <br /> Other <br /> Tank Primary Level Gauge Type Electronic <br /> Tank Primary Level Gauge Manufacturer/ eeder Root TLS-350 <br /> Model No. <br /> Tank Primary Level Gauge Condition Good <br /> Tank Primary Level Gauge Accuracy Good <br /> Tank Secondary/Interstitial Level Gauge Type Electronic Sensor <br /> Tank Secondary/Interstitial Level Gauge eeder Root TLS-350 <br /> Manufacturer and Model No. <br /> Tank Secondary/Interstitial Level Gauge Good <br /> Condition <br /> Tank Secondary/Interstitial Level Gauge Good <br /> Accuracy <br /> Other <br /> Overfill Protection As Required Per 40 CFR Observations WF Comments/Recommendations <br /> Overspill112.8/ <br /> Tank Overfill Protection Type Audible Alarm <br /> Does the Tank Overfill Protection Operate As es <br /> Designed? <br /> Is the Overfill Alarm Set At 90%?Overfill <br /> prevention device set at 90%? es <br /> Other <br /> Overspill Protection Observations <br /> Overspill Protection Type None <br /> Overspill Protection Condition N/A <br /> Other <br /> 5 <br />