Laserfiche WebLink
Inspection <br />An STI SP001 formal external inspection that included visual examination was conducted. The inspection was completed on <br />10/2/2015. The tank is located at Martin -Brower, 4704 Fite Court in Stockton, CA. The following is a detailed report of the <br />inspection includinq findinqs and recommendations. <br />1.0 GenerailTank Information <br />General Information <br />•.Comments/Recommendations <br />Facility Name <br />Martin -Brower <br />Facility ID <br />MARTIN-BROWER <br />Compliance Records Available? <br />No <br />Tanknology Work Order No. <br />6700447 <br />Other <br />Tank Data <br />Observations <br />Comments/Recommendations <br />Tank Nameplate <br />Yes <br />Waste oil/containment solutions no. r-51799 <br />Tank Name / Number <br />3 <br />Tank Layout (Horizontal, Vertical, other) <br />Horizonal <br />Tank Design (Single wall, double wall, other) Double Wall <br />Tank Construction Material (carbon, <br />Carbon <br />stainless, other) <br />Tank size (nominalgallons) <br />500 <br />Tank Shape <br />Rectangle <br />Tank Length <br />57" <br />Tank width / diameter / circumference <br />59" <br />Tank Height <br />5" <br />Tank Contents <br />Waste oil <br />Cathodic Protection <br />None <br />Continuous Release Detection Method <br />Elevated <br />CRDM <br />Release Prevention Barrier (RPB) <br />Concrete Floor <br />Spill Control <br />Double Wall <br />Other <br />Foundations And Supports <br />Observations <br />CommentslRecommendations <br />Tank Foundation Type <br />Concrete floor <br />Tank Foundation Condition <br />Good <br />Tank Support Type <br />Steel beams/footings <br />Tank Support Condition <br />Good <br />Tank Protection (bollards, fence, other) <br />Inside maint. building <br />Other <br />Signage As Required By NFPA 30 <br />•.Comments/Recommendations <br />Filling Procedures Posted At Fill As <br />Install signage at the fill point to document filling <br />Required? <br />No <br />procedures. ** <br />"No Smoking" Signage Present As Required Yes <br />Emergency Contact Numbers Posted As <br />No <br />Emergency plan is required and should include posting <br />Required? <br />of emerqency contact numbers. ** <br />Tank Capacity And Tank ID Posted On The <br />Yes <br />Tank As Required? <br />NFPA Signage - On The Tank, At Facility <br />Entrance, And As Designated By Fire Code <br />Official. Labels Include Contents And NFPA <br />es <br />704 Diamond Hazard Signs. <br />Other <br />