Laserfiche WebLink
5. <br />IExternal Coatings•.Comments/Recommendations <br />Tank External Coating <br />Paint <br />External Coating Condition <br />Good <br />Other <br />SheH <br />Condition Of Welds <br />O.Comments/Recommendations <br />Good <br />Corrosion <br />No <br />Evidence of Distortion <br />No <br />Mechanical Damage <br />No <br />Evidence of Leaks <br />No <br />Re ads or Changes to Original Desi n? <br />No <br />Other <br />Insulation <br />Insulation Missing? <br />•.Comments/Recommendations <br />N/A <br />Evidence of Moisture? <br />N/A <br />Evidence of Mold? <br />N/A <br />Damage to Insulation? <br />N/A <br />Corrosion Under Insulation? <br />N/A <br />Other <br />Standing Water low areas)? <br />69'e'rvations Comments/Recommendations <br />INo <br />Coating Failure? <br />jNo <br />Other <br />The tank is equipped with spill control and/or CRDM (continuous release detection method <br />and is considered a Category 1 tank per table 5.5 of STI SP001. The next formal inspection <br />would be required in 20 years or as required by the sites SPCC Plan. The inspection <br />I Inspection Is Required in (years): schedule is based on the site completing the recommended repairs as noted in the <br />inspection report. If problems are identified during periodic inspections a formal inspection <br />may required soon. The condition of the equipment may change after the issuance of this <br />er <br />