Laserfiche WebLink
Recommendations Letter <br /> Formal External Inspection of AST-4 <br /> Valley Pacific Petroleum Services,Inc. <br /> Page 2 <br /> • The tank's long-bolt manway is an approved Emergency Relief Vent(ERV);however,the stamped <br /> plate did not identify the overpressure venting capacity. <br /> • Water-finding paste was used to determine if water was present in both compartments of the tank. <br /> Water was not found in either compartment of the tank. <br /> Shell Testing <br /> Ultrasonic Thickness(UT)measurements were recorded in order to establish an inspection baseline for use <br /> during future inspections with the purpose of identifying corrosion.Measurements and visual inspection of <br /> the tank shells revealed no internal or exterior corrosion. Refer to Figure 1, Attachment A, for thickness <br /> measurements and photographs attached to the formal report. <br /> Recommendations for Continued Use <br /> Based on current industry practices and regulatory requirements, Condor recommends the following: <br /> • Periodic inspection and maintenance of the normal vents by Facility personnel is recommended for <br /> proper vent operation. <br /> • Periodic checks for proper emergency vent operation are recommended. During Condor's <br /> inspection,the tank's long-bolt manway covers did not lift easily and may have been inadvertently <br /> sealed. <br /> • Installation of an overfill valve and/or a basic high liquid level vent whistle(alarm)is recommended <br /> in order to prevent overfill. <br /> • Perform and document monthly and annual inspections in accordance with the Facility SPCC Plan. <br /> These recommendations should be implemented as soon as feasible.If you have any comments or questions, <br /> please contact us at(209)234-0518. <br /> Sincerely, <br /> CONDOR EART <br /> or n J hnson,AS Inspector No. AST-T10388 <br /> nvironm tal S Ialist <br /> XAProject\7000_prj\7167 valley Pacific Petroleum NONA Support\7167C Stockton\7167C2 Tank Inspections\Reports\AST4\FR 20181001 FEIR AST-4.docx <br /> �,� CONDOR <br />