Laserfiche WebLink
Vaporless LD -2000 Addendum„ <br />Table 2. Summary of the Test Results and Limitations AUG 2 2 2017 <br />Parameter <br />Probability of Detection for a 3 gal/h leak <br />Confidence Limits <br />Probability of False Alarm <br />Confidence Limits <br />Time to Conduct a Test <br />Maximum Applicable Rigid Line Size <br />Maximum Applicable Flexible Line Size <br />Page 8 <br />Value <br />100% <br />69 to 100% <br />0% <br />0 to 39% <br />< 1 minute to 20 minutes <br />depending on line <br />conditions <br />170 gallons <br />39.5 gallons <br />