Laserfiche WebLink
(b) By December 22, 2998, all underground piping containing motor vehicle fuel and <br /> connected to an existing tank shall be retrofitted with secondary containment unless the <br /> owner or operator demonstrates to the local agency that the piping is constructed of <br /> fiberglass reinforced plastic, catholically protected steel, or other materials compatible <br /> with stored products and resistant to corrosion. The secondary containment system shall <br /> meet the construction, installation, and monitoring requirements of section 2636. <br /> (c) By December 22, 1998, all automatic line leak detectors for underground pressurized <br /> piping which is not secondarily contained shall be capable of shutting off the pump when a <br /> release occurs. In addition, the pumping system shall shut down automatically if the <br /> automatic line leak detector fails or is disconnected. in lieu of the above, for <br /> underground storage tank emergency generator systems, the leak detector must be connected <br /> to an audible and visible alarm to indicate a release malfunction of the system. <br /> (d) All underground piping and secondary containment shall be tested for tightness after <br /> installation in accordance with section 2636(e) . <br /> If you have any questions please contact me at (209) 468-0332 <br /> Karen Furst, M.D. , M. P.H. <br /> Health Officer <br /> vre- <br /> Robert McClellon, R. E.H. S . <br /> Environmental Health Division <br /> cc : Satnum Singh <br /> Enclosures : <br />