Laserfiche WebLink
0 <br />Hydrostatic Design met by UL 142 listing. <br />Seismic/Anchoring findings: The tank as de ned and operated, and the <br />containment area in which it is located are ade tely anchored and are <br />seismically sound. Initials: <br />Leak Test: The tank is in service. Visual inspection of the tank and ancillary <br />equipment did not show any signs of leakage. The tank interstice was clean and <br />dry on inspection. The tank is a double walled above ground storage tank. Ultra <br />sonic thickness testing of the secondary tank exceeds the required U.L. 142 <br />minimum tank wall thickness. <br />Integrity testing findin s: Based on the above noted integrity test and the <br />results obtained from 9441 test, the tank has sufficient integrity for its intended <br />use. Initials: <br />Tank Drawing: <br />Stockton Nissan <br />Waste Oil Storage Tank <br />Mfg Containment 5olutinns <br />1000 gallons <br />Ut 142 <br />Integral Secondary Containment <br />Date of Manufacture: 2008 <br />110" 46" <br />I 95 F— — — 43" <br />:T <br />I I Y I <br />I I I I <br />I I P I <br />I I f I <br />57" <br />I I I I <br />I I I I <br />1 <br />I - - - - - - - - - - a - - - - - - - - - -I <br />I I I I <br />I <br />� - - 0 s 1 <br />Facing North <br />Stockton Nissan Waste Oil Storage Tank <br />