Laserfiche WebLink
QUALITY CONTROL REPORT, CONTINUED <br /> OCTOBER 1, 1992 <br /> TREATEK <br /> SAMPLE LOG #16124-92I THROUGH 16128-92I <br />' DATE EXTRACTED: SEPTEMBER 28 , 1992 <br /> DATE ANALYZED: SEPTEMBER 28, 1992 <br /> EXTRACTION METHOD: 5030 <br /> ANALYSIS METHOD: 8020 <br /> Concentrations were calculated using a 4 point curve of <br />' concentrations 2 . 5 , 5, 10 and 20 ppb. <br /> LABORATORY CONTROL STANDARD <br /> A 20 ppb standard verification was run in the sample set up. <br />' METHOD BLANK <br /> NO TARGET ANALYTES WERE DETECTED IN METHOD BLANK. <br />' LCS <br /> COMPOUND %RECOVERY <br />' Benzene 84% <br /> Toluene 82% <br /> Ethylbenzene 86% <br /> Xylenes 85% <br /> SPIKE DATA <br /> A QAL Method Blank was spiked in duplicate with 20 ppb 8020 <br /> standard. <br />' COMPOUND SPIKE RELATIVE <br /> % RECOVERY % DIFFERENCE <br />' Benzene 85% 3% <br /> Toluene 83% 0% <br />' Ethylbenzene 87% 0% <br /> Xylenes 86% 0% <br /> I <br /> y X/IL 1M <br />' YVETTE J. LIEBESMAN <br /> QA SPECIALIST <br /> I <br /> QUALITY CONTROL TERMINOLOGY <br /> •LCS - LABORATORY CONTROL STANDARD REPORTED AS % RECOVERY OF AN INDEPENDENT STANDARD CARRIED THROUGH ALL <br /> SAMPLE PREPARATION PROCEDURES TO VERIFY METHOD PERFORMANCE ACCEPTABLE RANGE IS BASED ON HISTORICAL <br /> LABORATORY CONTROL DATA, BUT IS GENERALLY WITHIN A 80%-120% RECOVERY RANGE. <br />' •SPIKE - ENVIRONMENTAL SAMPLE IS MATRIX SPIKED WITH METHOD COMPOUNDS AND % RECOVERY OF CONCENTRATION SPIKED <br /> INTO SAMPLE IS CALCULATED REPORTED AS % RECOVERY ACCEPTABLE RANGE FOR "NORMAL MATRIX SAMPLE" IS BASED ON <br /> HISTORCCAL LABORATORY CONTROL DATA, BUT IS GENERALLY WITHIN A 75%-125% RECOVERY RANGE. <br /> •SURROGATES - COMPOUNDS REPRESENTATIVE OF A GROUP OF COMPOUNDS SURROGATES ARE SPIKED INTO ENVIRONMENTAL <br />' SAMPLES AND % RECOVERY OF CONCENTRATION SPIKED IS CALCULATED AND REPORTED. ACCEPTABLE RANGE VARIES DEPENDING <br /> ON SAMPLE MATRIX AND ANALYSIS METHOD. <br />