Laserfiche WebLink
Volume calculation: The tank has integral secondary containment with <br /> ' continuous monitor of the interstice. The piping is in doors under roof over a <br /> sealed concrete slab foundation. The line volume is 6 gallons. If the entire line <br /> drained on to the floor it would form a spill 10' diameter and 1/8" deep. The <br /> tgarage has sufficient materials to contain and clean the spill if it should happen. <br /> tDesign of containment area: <br /> ' The tank is a Lube Cube manufactured by Containment Solutions. These tanks <br /> normally have a UL 142 placard on them but it is missing on this tank. The tank <br /> has integral secondary containment which is dry and clean. The tank is within a <br /> petroleum storage room which has a bermed doorway to prevent any spill from <br /> line failure or transfer operations from leaving the immediate area. The transfer <br /> piping is welded copper which is inspected daily during business hours. The <br /> ' piping is indoors, above ground and over a sealed concrete floor. The tank has a <br /> continuous interstice monitor and overfill alarm sensor set at 90% of the tank <br /> volume. These points are alarmed by a visual and audible alarm in the garage. <br /> ' Site Security: The transfer lines and tank are indoors and access is locked during <br /> non-business hours. The dealership is regularly patrolled by the Tracy Police <br /> ' Department. <br /> ' Secondary Containment findings: The secondary containment systenuls of <br /> sufficient capacity and condition for the containment of releases from all nks <br /> and ancillary equipment. Initials: <br /> 1 <br /> 1 <br /> 1 <br /> ' Tracy Hyundai 16 Oil Tank <br />