Tracy Hyundai <br /> 1 Cylindrical Closed Top <br /> Material of Construction: LDPE <br /> Shell Height,in 48.000 <br /> Shell Diameter,in. 36.000 <br /> ' Volume of Tank,in3 48833.280 <br /> Volume of Tank,gallons 211.399 <br /> Working Volume,gal 190.260 <br /> S.G.of contents 1.050 <br /> Weight of Contents,lbs 1666.103 <br /> Tank Wall Thickness,mm 7.300 <br /> Tank Wall Thickness,in 0.287 <br /> Wt of Tank, lbs 71.235 <br /> Total Weight of Tank and Contents,lbs 1737.338 <br /> Zip Code 95304 <br /> Height of CG,in 24.000 <br /> Overturning Moment Arm,in 24.000 <br /> Resisting Moment Arm,in 18.000 <br /> Soil Class D <br /> Fa 1.000 <br /> Fv 1.530 <br /> Sms 1.440 <br /> SmI 0.720 <br /> Sds 0.960 <br /> Shc 0.480 <br /> To 0.100 <br /> Ts 0.500 <br /> E,LDPE,psi 29000.000 <br /> I,in4 5263.036 <br /> k,Ibflin 33122.403 <br /> T,sec 0.878 <br /> T>To Non-rigid structure <br /> Sa 0.547 <br /> Importance Factor 1.000 <br /> ' Seismic Shear Force,Ibf 949.778 <br /> Overturning Moment,inlbf 22794.664 <br /> Resisting Moment,inlbf 31272.080 <br /> Resisting Moment>Overturning Moment <br /> No Tension on Anchors <br /> Number of Anchors for Shear 1.000 <br /> Shear Strength of Anchor.Lbs Trubolt, 112"wedge,3"embdmnt 4760.000 <br /> ' Factor of Safety for Shear 5.012 <br /> Seismic/Anchoring findings: The tank as design and operated, and the <br /> containment area in which it is located are adequa anchored and are <br /> seismically sound. Initials: <br /> Leak Test: Tank has been in service for five years. Visual inspection did not <br /> show any evidence of tank leakage, weld cracks or corrosion. UT analysis snows <br /> the tank to be in as built condition. <br /> Tracy Hyundai 7 Antifreeze Tank <br />