Volume calculation: The waste antifreeze tank is located indoors in a <br /> containment area of 13.3' x 16' x .5' which gives a gross containment volume of <br /> 795 gallons. However some of the containment is occupied by other tanks. This <br /> loss of containment volume is less than 250 gallons. Thus the net containment <br /> volume is 545 gallons. The waste antifreeze tank is the only tank which requires <br /> this containment. All the other tanks have integral secondary containment. The <br /> working volume of the waste antifreeze tank is 190 gallons. The percentage <br /> containment of this tank is 287 percent. The waste antifreeze transfer line and <br /> the waste antifreeze line volume is less than three gallons. Therefore the <br /> containment provided is sufficient for the present use. <br /> Design of containment area: <br /> The containment area is at grade and is provided by a concrete floor and walls <br /> with a bermed doorway. The tank is within a petroleum storage room which has a <br /> bermed doorway to prevent any spill from line failure or transfer operations from <br /> leaving the immediate area. The transfer piping is welded copper which is <br /> inspected daily during business hours. The piping is indoors, above ground and <br /> over a sealed concrete floor. The tank has an overfill alarm sensor set at 90% of <br /> the tank volume. These points are alarmed by a visual and audible alarm in the <br /> garage. The containment area is monitored several times per day by the garage <br /> staff. <br /> Site Security: The transfer lines and tank are indoors and access is locked during <br /> non-business hours. The dealership is regularly patrolled by the Tracy Police <br /> Department. <br /> Secondary Containment findings; The secondary containment syste s of <br /> sufficient capacity and condition for the containment of releases from all nks <br /> and ancillary equipment. Initials: <br /> Tracy Hyundai 13 Antifreeze Tank <br />