fAqu4d j SERVICE ORDER <br /> 111 <br /> Service Company <br /> ' CUSTOMER Tracy Chrysler Hyundai DATE 18 Aug 2009 <br /> 3460 Naglee Rd. TIME <br /> Tracy, CA 95304 BY Larry <br /> CONTACT Ron Im eriale P.O. # <br /> PHONE 209-820-1800 NEXT SERVICE <br /> ! <br /> SERVICE ORDER: <br /> Chrysler dealership: Tested High Level Alarm and Secondary Containment <br /> Alarm for Waste Oil and Waste Antifreeze tanks. Extended Waste Oil secondary <br /> level sensor to about 2" from bottom of tank (was set at about 3 feet from <br /> bottom). Replaced blown fuse in Waste Oil alarm l2anel. New bulb needed for <br /> Secondary Containment Alarm light on the Waste Oil alarm panel. Tested all <br /> ! four sensors/alarms to be functional. Applied temporary identification tape for <br /> the alarm lights to indicate "high" and "secondary" alarms. Permanent labels <br /> need to be applied. <br /> Hyundai dealership: Tested High Level Alarm for the Waste Oil and <br /> Waste <br /> Antifreeze tanks. Both alarms tested good. Furnished and installed Simpson <br /> HL33A seismic restraint clips, 10 total, to restrain the Waste Oil and Waste <br /> Antifreeze tanks. Clips anchored using 1/2" diameter concrete wedge anchor <br /> ' bolts with 3" embedment depth. <br /> ! COMMENTS <br /> CUSTOMER SIGNATURE DATE _ <br /> Aquadynamics Service Co. <br /> ' 1221 Park Ave., Ste. A, San Jose, CA 95126 Ccll (408) 591-6127 <br /> Tracy Hyundai 19 Antifreeze Tank <br />