Laserfiche WebLink
ensure that the excavation site is secured prior <br /> to his departure. <br /> C. RE <br /> M_f?VAL - LOCAL ENVIRONMENTAL HEALTH SHALL: <br /> " Inspect the tank after its removal from the <br /> excavation for evidence of leaks or corrosion. <br /> ` Inspect the excavation of preliminary evaluation <br /> of product release or soil contamination. <br /> " Direct the collection of soil samples from the <br /> excavation. <br /> * Initiate any required clean-up action. <br /> II. TANK IN ALLATION: <br /> A. Local Building Department or Fire Department <br /> Inspect: <br /> Dispenser installation, shear valves, fire <br /> extinguisher installation, emergency shut off <br /> switch location and operation, vent lines, swing <br /> joints, location of tank openings and appropriate <br /> cover. <br /> B. Local Environmental Health shall: <br /> Witness holiday test of fiberglass coated tanks <br /> prior to placement in the excavation and <br /> document test results on the job-site card. <br /> * Witness the pressure test of lines and tanks <br /> and document test results on the job-site <br /> card. <br /> * Inspection the monitoring/leak detection <br /> system. <br /> Review the results of precision test. <br /> - 21 - <br />