Laserfiche WebLink
PUBLIC <br />HEALTH SERVICES <br />sAN JOAQUIN COUNTY �- <br />ENVIRONMENTAL HEALTH DIVISION <br />Karen Furst, M.D., M.P.H., Health Officer t' <br />4lspR <br />304 East Weber Avenue, Third Floor • Stockton, CA 95202 <br />2091468-3420 <br />MEMORANDUM <br />Date: 6!23/1998 <br />To: Lou Hollman, Job Captain <br />RHL Design Group, Inc. <br />From: Michael Kith, Sr. REHS <br />San Joaquin County ' <br />Environmental Health Division (EHD) <br />Re: 7 -Eleven, 2725 Country Club Blvd, Stockton. <br />The following information is needed for the approval of your applicatiorofor permit to <br />install and to remove underground storage tanks (UST) at above location: <br />1. Installation <br />1. Manufacturer's tank installation instruction manual, not installation practices. <br />2. Please specify the teak detector to be installed; page SD -3, item 13.10 of the <br />plan shows electronic line leak detector; page G-5, item 10 of the plan shows <br />LD2000E; the application shows LD2000. <br />I In the plan, the cross sectional diagram of the tank shows asingle-walled tank. <br />The cut -sheet and application show double -walled tanks. Please clarify and <br />submit cross sectional diagram of a double -walled tank., including the location <br />of interstitial sensor. <br />4. Specification and cut -sheet for tank sump sensor. <br />5. Page G-11 of the plan shows Red Thread II or Arneron fiberglass pipes. <br />Please specify. <br />6. Buoyancy calculation. <br />II. Removal <br />1. Site EPA number. <br />Please submit the above information to EHD. If you shall have any questions please <br />contact me at 209-468-3444. <br />A Division of San Joaquin Counry Health Care Services <br />