Laserfiche WebLink
Test Date: 12 May 19 9 3 <br />LEAK DETECTOR DATA <br />Work Order# : 9 610 0 2 <br />FAILED LEAK DETECTORS <br />Tank 1 <br />Tank 2 <br />Tank 3 <br />Tank 4 <br />Tank 5 <br />Tank 6 <br />Serial dumber: <br />1 <br />2 <br />3 <br />Product: <br />UNLEAD <br />PLUS <br />PREMIUM <br />Leak Detector <br />manufacturer: <br />REDJACKET <br />REDJACKET <br />REDJACKET <br />Leak detector model: <br />P.L.D. <br />D.L.D. <br />D.L.D. <br />Leak detector <br />serial number: <br />110894424 <br />10188---- <br />111860405 <br />Open time - sec: <br />3 <br />5 <br />5 <br />Element holding -psi: <br />10 <br />13 <br />13 <br />Resiliency - cc: <br />320 <br />110 <br />100 <br />Leak calibration -cc: <br />252 <br />252 <br />252 <br />Leak Rate - GPH: <br />4.00 <br />4.00 <br />4.00 <br />Metering PSI: <br />10 <br />10 <br />10 <br />Detected Leak (Y/N): <br />YES <br />YES <br />YES <br />Pass/Fail: <br />PASS <br />PASS <br />PASS <br />FAILED LEAK DETECTORS <br />LEAK DETECTOR TEST COMMENTS: <br />NDE Environmental Corporation - 20000 Mariner Avenue Ste 500 - Torrance, CA. 90503 - (310) 542-4342 Page 4 <br />Tank 1 <br />Tank 2 <br />Tank 3 <br />Tank 4 <br />Tank 5 <br />Tank 6 <br />Leak Detector <br />manufacturer: <br />Leak detector model: <br />Leak detector <br />serial number: <br />Leak Rate - GPH: <br />Pass/Fail: <br />LEAK DETECTOR TEST COMMENTS: <br />NDE Environmental Corporation - 20000 Mariner Avenue Ste 500 - Torrance, CA. 90503 - (310) 542-4342 Page 4 <br />