Laserfiche WebLink
SWRCB,January 2002 page 2. <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: F Tank Manufacturer ❑X Industry Standard Professional Engineer <br /> El Other (Specify) <br /> Test Method Used: FI Pressure El Vacuum El Hydrostatic <br /> 11 Other (Sped) <br /> Test TcjifiPment I;sed: Equipment Resolution: <br /> lank# Dank # i <br /> Tank # "Tank# <br /> Is Tank LxC mpt 1-1-0111"1 estlig:' Yes X❑No Yes No ❑ Yes No --[:]Yes ° o <br /> Tank Capacity: 10, 000 10, 000 <br /> Tank Material: DW STEEL DW STEEL <br /> Tank Manufacturer: unknown unknown <br /> Product Stored: REG UNLEAD PREMIUM <br /> Wait time between applying <br /> pressure/vacuum/water and 5min 5min <br /> starting test: <br /> Test Start Time: 15:50 16:42 <br /> Initial Reading(Rt ): 10hg 10hg <br /> Test End Time: 16:50 17:42 <br /> Final Reading(RF }: 9.5hg 9hg <br /> Test Duration: lhr 1hr <br /> Change in Reading(RF -Rt }: .5hg lhg <br /> Pass/Fail Threshold or Criteria: 2hg 2hg <br /> Test Result: E Pass Q Fail [E] Pass E Fail 0 Pass El Fail E]Pass El Fail <br /> Was sensor removed for testing'? E]YesE]NoE]NA �{ Yes NoE]NA Yes No❑NA❑Yes�No�NA <br /> Was sensor properly replaced and ❑ � � 0 <br /> verified functional after testing? FlYeSEINCEINA X Ye N NA Ye N NA Ye N NA <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> t Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)} <br />