Page 1 of 1 <br /> TANK ANNULAR TESTING <br /> Test Method Developed By: r Tank Manufacturer r Industry Standard r Professional Engineer <br /> F Other(Specify) <br /> Test Method Used By: r Pressure r vacuum r Hydrostatic <br /> F_Other(Specify) <br /> Test Equipment Used:gauge Equipment Resolution:.20" <br /> Tank# T1 Tank# T-2 Tank# <br /> Is Tank Exempt From Testing?' r Yes r No r Yes r No r Yes r No <br /> Tank Capacity: <br /> 10000 10000 <br /> Tank Material: Steel Steel <br /> Tank Manufacturer: total containment total containment <br /> Product Stored: PUL RUL <br /> Wait time between applying 5 min 5 min min <br /> pressure/vacuum/water and starting test: <br /> EFinalReading <br /> Time: 19:30:00 19:30:00 <br /> Reading(RI): 15.00000 in. HG 15.00000 in. HG <br /> ime: 08:50:00 08:50:00 <br /> (RF): 7.00000 in. HG 8.00000 in.ion: 12.4 hr 12.4 hr <br /> Change in Reading(RF_R): -8.00000 in. HG -7.00000 in. HG <br /> Pass/Fail Threshold or Criteria: +/-5,00000 +/-5.00000 +/- <br /> Test Result: Fail Fail <br /> Was sensor removed for testing? r Yes r Nor NA IT Yes r Nor NA r Yes r Not' NA <br /> Was sensor properly replaced and verified r Yes r Nor NA r Yes r Nor NA r Yes r No r NA <br /> functional after testing? <br /> Comments?(include information on repairs made prior to testing. and recommended follow-up for failed tests) <br /> both test were started at 19:30 on 4-8-13 and ended on 4-9-13 at 8:50. <br />