r • • <br /> LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2309058 Date: 2/20/2013 <br /> Site Name/ID: 7-ELEVEN#14117, MKT 2368/ 14117 <br /> Address: 2725 COUNTRY CLUB BLVD <br /> City: STOCKTON State: CA Zip: 95204 <br /> ank lD T1 T-2 <br /> roduct PUL RUL <br /> roduct Line 1 1 <br /> ested From 1 1 <br /> xisting/New Existing Existing <br /> echanical/Electronic Mechanical Mechanical <br /> ManufacturedModel Vaporless LD-200 Vaporless LD-200 <br /> anal No. 04011558 ----1983 <br /> ump operating Pressure(psi) 31.00 29.00 <br /> alibrated Leak(ml/min) 189.0 189.0 <br /> alibrated Leak(gph) 3.00 3.00 <br /> oiding PSI 30.00 29.00 <br /> NIA for Electronic Le's <br /> Resiliency(ml) 75.00 105.00 <br /> NIA for Electronic Lo's <br /> ---- <br /> Metering PSI 22 10 <br /> NIA for Electronic LD's <br /> Opening Time(sec) 3 3 <br /> NIA for Electronic LD's <br /> est Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Timothy Elebeck certification#: 1707 <br /> � � � Expire Date: 8/16/2014 <br /> Technician Signature: <br /> Environmental Compliance for Petroleum Systems <br /> c 2013 Twlmdogy lnc.,Austn,TX. Alln9his rss Nm tanktalo9y.mm <br />