Laserfiche WebLink
A • Page 1 of 1 <br /> SPILUOVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Fill Riser Containment Sumps r <br /> Fill Riser Containment Sumps are Present, but were Not Tested r <br /> Test Method Developed By: C Spill Bucket Manufacturer 170 Industry Standard r Professional Engineer <br /> r Other(Specify): <br /> Test Method Used By: r Pressure r vacuum C+ Hydrostatic <br /> r Other(Specify): <br /> Test Equipment Used: I_LAKE TEST Equipment Resolution: „OA625 in. <br /> Spill Box# Spill Box# <br /> Tank T1 PUL Tank T-2 RUL Spill Box# Spill Box# <br /> Fill- Direct Fill-Direct <br /> audtet Darrater 12.00 12.00 <br /> Bucket Depth: 12.00 12.00 <br /> wait time between applying 5 min 5 min min min <br /> pressurety o urnwaterand staring test <br /> Test Start rim 09:15:00 09:15:00 <br /> Initial Reading two 12.50 in. H2O 12.25 in. H2O <br /> Test End Time: 10:15:00 10:15:00 <br /> Final Reading tet: 12.50 in. H2O 12.25 in. H2O <br /> Test Duretion: 1 hr 1 <br /> Change in Rees ingm,w: 0.00 in. H2O 0.00 in. H2O <br /> PasslFail Threshed a Critena: +1-0.00 +/-0.00 +/- +/- <br /> Test Result: Pass Pass <br /> Comments 7 (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2309058 <br />