Laserfiche WebLink
0 0 <br />LDT 5000 !Field "est Apparatus <br />f, Tank oiogy Line Leak Detector Test <br />Work Order: <br />Site Name 1 ID <br />Address: <br />City: <br />2309194 <br />CHEVRON 210997 (N-4693)1210997 <br />1442A COLONY DR. <br />RIPON <br />Date: 2/712013 <br />Page 1 of 1 <br />State: CA Zip: 95366 <br />Tank ID <br />Ti -SUPREME UNLEADED <br />2:REGULAR UNLEADED <br />Product <br />PREMIUM <br />REGULAR <br />Product Line <br />1 <br />1 <br />Tested From <br />1 1 <br />11 <br />Existing/New <br />Existing <br />Existing <br />Mechanical/Electronic <br />Electronic <br />Electronic <br />ManufacturerlModel <br />Veeder Root PLLD <br />Veeder Root PLLD <br />Serial No. <br />189503 <br />189451 <br />Pump Operating Pressure (psi) <br />26.00 <br />27,00 <br />Calibrated Leak (ml/min) <br />189.0 <br />189,0 <br />Calibrated Leak (gph) <br />3.00 <br />3,00 <br />Holding PSI <br />NWA for Electronic Lo's <br />Resiliency (ml) <br />NWA for Electronic Lo's <br />Metering PSI <br />NWA for Electronic Lo's <br />Opening Time (sec) <br />NWA for Electronic Lb's <br />Test Results <br />Pass <br />Pass <br />Technician Comments: <br />Technician Name <br />Technician Signature: <br />Jarrod Cooke Certification #: 1352 <br />Expire Date: 2/14/2013 <br />Environmental Compliance for Petroleum Systems <br />C 2013 Tankndogy Inc., Austin, TX. All rights reserved. tanknology.corn <br />