Laserfiche WebLink
D. Results of Testing/Servicing <br /> Software Version Installed: <br /> Complete the following checklist: <br /> ®Yes ❑No* Is the audible alarm operational? <br /> ®Yes ❑No* Is the visual alarm operational? <br /> ®Yes ❑No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ❑Yes ®No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> ®Yes ❑No* If alarms are relayed to a remote monitoring station,is all communications equipment(e.g. modem)operational'? <br /> ❑NIA <br /> For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ Yes ❑No* monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate <br /> C9 NIA positive shut-down? (Check all that apply) ❑Sump/Trench Sensors; ❑Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? ❑Yes ❑No <br /> ❑Yes ❑No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br /> ®N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank fill <br /> point(s)and operating properly? If so, at what percent of tank capacity does_ the alarm trigger? % <br /> ❑Yes* 9 No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> [] Yes* ®No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> Product; ❑Water. If yes, describe causes in Section E,below. <br /> Yes Lj No* Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports, if applicable <br /> CK Yes ❑No* Is all monitoring equipment operational per manufacturer's specifications? <br /> In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: 5,000 above ground, transition box sump and sensor turbine sensor needs to be moved to <br /> lowest position. Turbine lid is missing sump bolts. Tecnician had to change the time on the <br /> monitor clock. oni or is direct monitor at office. Technician was in contact witri the ofrice <br /> (through tho Wlephene) while, flipping r5emggr_P:. San )r the bracket. ed-s- -:a <br /> ZP <br /> strap bracket. <br /> Page 2 of 3 03101 <br />