Laserfiche WebLink
41 `OIL EQUIPMENT SERVICE Ainlay Tank 'Tegrity Tester <br /> D:vlslon"of Keith A.Tapia Inc. REPOR 1 <br /> 750 Industrial Way- P. 0. Box 950 " r <br /> SAN ANDPEAS, CALIF. 95249 Date 7-9-86 <br /> (269)784-1808 <br /> Company Sav-Mor Oil #307 Address 4579 E . Acampo Rd . , Acampo <br /> Nrand Name Grade of Product Premium <br /> Gallons 8133 API Gravity 56 .09 Coefficient of Expansion •00066 <br /> Coefficient of expansion x gallons = Factor to be used in this test for each <br /> degree of temperature shift <br /> Factor 5 . 36778 <br /> Test IFS 3 <br /> Thermometer Net Change Temperature shift • 0175 <br /> Shift due to <br /> Start End + or - Temp. only Times Factor = • 0939 <br /> Time 4 :40 5: 40 <br /> Temperature shift times <br /> 111 Top 88 .09 88 . 10 + .01 x 25% 0025 factor equals volume <br /> change due only to <br /> 112 Mid. 82. 65 82 .65 0 x 50% 0 Temperature change <br /> 43 Bottom 78. 88 78 .94 + . 06 x 25% .015 Oor - .0939Gallons <br /> Amount added or removed <br /> to get Slope tube back <br /> to starting point•066 <br /> Ne loss r gain <br /> gallons <br /> Test 112 <br /> Thermometer Net Change Temperature shift <br /> Shift due to <br /> Start End + or - Temp. only Times Factor = <br /> Time <br /> x 25% Temperature shift times <br /> 111 Top factor equals volume <br /> change due to <br /> U2 Mid. x 50% Temperature change <br /> + or - Gallons <br /> 1i3 Bottom x 25% <br /> Amount added or removed <br /> Note: NEPA in Publication 11329, 4-3.10.0 does not call for a to get slope tube back <br /> precision test to show a loss of more than .05 gallons to starting point <br /> (189ml) per hour. Net loss or gain <br /> Therefore, since tested tank to gain of (line 13) gallons <br /> •0279 gallons per hour i DOES OES NOT meet NFPA <br /> criterion for tank tightness. (� <br /> Tester e. y SIS <br />