ISM-4080 and ISM-4081 Specifications
<br /> For Use With:
<br /> • 99 LD-2000, 99 LD-3000 Mechanical Line Leak Detectors.
<br /> Leak Detector Sensor Housing,
<br /> Part # ISM-4101 and Part # ISM-4102 are constructed of:
<br /> • 6061 T-6 Aluminum
<br /> • All Aluminum is Hard Anodized
<br /> • Viton 0-rings are compatible with: Gasoline, Methanol and Ethanol (all blends through 100%),
<br /> MTBE through 15% concentrations, #1 or#2 Diesel, Kerosene, Jet A, JP-4,AV Gas, and Biodiesel
<br /> • Switch is approved for total immersion in above liquids.
<br /> Leak Detector Sensor Housing Dimension:
<br /> • Height: 2 318", 61 mm
<br /> ISM Controller Housing Dimensions:
<br /> • Length: 3112", 89mm Width: 4118", 105mm Depth: 2 114", 57mm
<br /> Input Voltage:
<br /> 115 Vac, 50160 Hz, single phase, control circuit current 40 ma
<br /> • 230 Vac, 50160 Hz, single phase, control circuit current 20 ma
<br /> • Input voltage is selectable by choice of external wiring
<br /> Authorization Input Voltage Range:
<br /> • 60 - 240 Vac
<br /> Output Relay Rating:
<br /> • Ready Relay for Solenoid Valve Control 8 amp, 1251250 Vac: 5 amp, 30 Vdc
<br /> • Exterc
<br /> For use with intrinsically safe input, an isolation relay is needed.
<br /> Sensor Input:
<br /> • Piston Switch may share the same wire pair as a single pole, normally closed, sump sensor compatible with
<br /> intrinsically safe circuitry. Intrinsically safe voltage and current supplied from the ISM-408014081 to the Piston
<br /> Switch and Sump Sensor Circuits, for hazardous locations, Class 1, Group D. Wiring for sensors shall not be in
<br /> the same conduit as high voltage wiring, nor installed in any way as to allow sensor wiring to current that is not
<br /> supplied by an intrinsically safe source.
<br /> Tank Monitor Disable Input Voltage Range:
<br /> • AC Type: 60-240 Vac - Typical AC Voltage: 115 Vac @ 10 ma
<br /> • DC Type: 5-24 Vdc - Typical DC Voltage: 24 Vdc @ 1 ma
<br /> Selectable Repressurization Delay, based upon Line Resiliency,Values in Minutes:
<br /> • 02, 05, 10, 15, 30, 45, 60, 75, 90
<br /> Selectable Duration (submersible run time),Values in Minutes:
<br /> • 00 (none), 01, 02, 03, 04, 05, 06, 07, 08, 09, 10
<br /> ISM-4080 and ISM-4081 Controller: CSA Approval Pending
<br /> Vaporless Manufacturing, Inc. Toll Free: 1-800-367-0185
<br /> VM1 8700 East Long Mesa Drive Phone: (928) 775-5191
<br /> Prescott Valley, Arizona 86314 Fax: (928) 775-5309
<br /> 02JOB Web Site: www.vaporiess.com 9 Email vmi@vaporiess.com
<br />
|