Laserfiche WebLink
STOCKTON SERVICE STATION EQUIPMENT CO. IN&4), <br /> 808 N. UNION STREET �pIRONSTOCKTON210pS <br /> CA 95205-4152 <br /> PHONE 09 464..83 3 FAX 09.464.8349 FRM/TS R 7CF8 Ty <br /> LDT-890 LEAK DETECTOR TEST RECORD <br /> CUSTOMER: G.I.TRUCKING DATE: May 06,2005 <br /> LOCATION: 7611 S.Airport Way <br /> CITY: STOCKTON STATE: CA ZIP:95206 <br /> TECHNICIAN: Eric Molgaard <br /> Submersible Pump Identification <br /> Manufacturer Model Serial Number <br /> Red Jacket 1-1/2 H.P. <br /> Leak Detector Identification <br /> Manufacturer Description Other Style Leak Detector <br /> F. E.Petro Model SPT-MLD-D Serial No. 03070653 <br /> Diaphragm-type <br /> Piston-type X <br /> Tamper-proof seal installed? Yes No X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 45 psi (para.15) (Purging Test System) <br /> 2. Gallons per hour rate 3 GPT 1 (para.22) (Leak Test,Phase I) <br /> 3. Line pressure with pump shut off 10 psi (para.23) (Leak Test,Phase 1) <br /> 4. Bleed-Back Test with pump off 100 ml (para.26) (Bleed-back Test) <br /> 5. Step-through time to full flow (para.30) (Step-throuh Test) <br /> 6. Leak detector stays in leak search position (para.42) Yes X No_ <br /> LEAK DETECTOR TEST <br /> Note: Pass—Leak detector fits test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Form 890C <br />