Laserfiche WebLink
From; 0 011 22009 17:04 #347 F.0101011 <br />0 rq Ttin c. r oris <br />RLC <br />" <br />PH J1 Elm" <br />EVi4'OF 9.3 - <br />9. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Page 9 <br />Test Method Developed By: _ UDC Manufacturer X industry Standard _' Professional Engineer <br />0 Other (Specify) <br />Test Method Used: i.7 Pressure -; Vacuum X Hydrostatic <br />Other (Sped) <br />Test Equipment Used: Ronan HY Precision Test Equipment Equipment Resolution: 0.0000" <br />Master 1/2 Master 4 Satellite 2 Satellite l Satellite 4 <br />UDC Manufacturer: Fiberglass Fiberglass Fiberglass Fiberglass Fiberglass <br />UDC Material: <br />Fiberglass Fiberglass <br />Fiberglass Fiberglass <br />Fiberglass <br />UDC Depth: <br />32" 32" <br />32" 32" <br />32" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />11 7" <br />10" 10" <br />—7" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />—91, _91" <br />—6" —6" <br />_91. <br />Condition of UDC prior to <br />Clean Clean <br />Clean Clean <br />Clean <br />testing: <br />Portion of UDC Tested' <br />--14' t a" <br />13" 14" <br />--14" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />xYes -_'No ryes F.,,No <br />xYes UNo xYes `No <br />xYes 7_7No <br />1JYes •.- No <br />product and water)?' <br />QNA DNA <br />INA _NA <br />!NA <br />DNA <br />Turbine shutdown response time <br />--6 sec --6 sec <br />—6 sec —6 sec <br />--6 sec <br />Is system programmed for fail- <br />xYes CNo xYes 1 -No <br />xYes DNo x'ltes ']No <br />xYes CJNo <br />C:Yes !'.,No <br />safe shutdown'?* <br />:'NA `-INA <br />uNA LINA <br />ONA <br />DNA <br />Was fail-safe verified to be <br />xyes i.:1No xYes -7No <br />xYes 3No xYes 1'!No <br />xYes 12 -No <br />.DYes ONo <br />operational?' <br />CNA :INA <br />f]NA r'NA <br />QNA <br />[_'NA <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />Test Start Time: <br />8:00 ani 8:00 am <br />9:00 am 9:00 am <br />10:00 am <br />Initial R.eadang (Rl): <br />Test End Time: <br />8:30 am 8:30 am <br />9:30 am 9:30 am <br />10:30 am <br />Final Reading (RF): <br />Test Duration: <br />30 minutes <br />Change in Reading (REr-RI). <br />0 0 0 1 0 0 <br />Pass/Fail Threshold or Criteria: <br />PASS =No Lass or Loss of 0.0020" or less in 30 minutes <br />Test R+ sulci <br />xPass ❑Fail <br />xPass ❑Fait <br />xPass ❑Fail <br />xPam DFaii <br />xPass ❑Fail <br />OPass ❑Fiil <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced and <br />Yes <br />Yes <br />Yes <br />Yes <br />Yes <br />verified functional after testing'? <br />Comments — (inchiele inl6 ntation on repairs made prior to testing, and recomniended,follotiv-tip for failed tests) <br />` If the entire depth of the UDC is not tested, specify how much was tested. if the answer to Agy of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />