Laserfiche WebLink
INDIVIDUA ANK/LINE/LEAK DETECTOR TE,REPORT <br />NDE ENVIRONMENTAL CORPORATION <br />TESTDATE: March 24, 1994 <br />CLIENT: UNOCAL OIL CORP <br />WORK ORDER NUMBER: 962338 <br />SITE: UNOCAL #4409 <br />TANK INFORMATION <br />Tank ID: 2 <br />Bottom to top fill in inches: <br />135.0 <br />Product: PREMIUM <br />Bottom to grade fill in inches: <br />143.0 <br />Capacity in gallons: 12,000 <br />Fill pipe length in inches: <br />40.0 <br />Diameter in inches: 95.00 <br />Fill pipe diameter in inches: <br />4.0 <br />Length in inches: 396 <br />Stage I vapor recovery: <br />COAX <br />Material: STEEL <br />Stage II vapor recovery: <br />BALANCE <br />Tank: No <br />Manifolded Vent: No <br />WR: YES <br />COMMENTS <br />TANK TEST: RESULTS <br />LEAK DETECTOR RESULTS <br />Test method: VPLT <br />New/passed <br />Failed/replaced <br />Psi at tank bottom: 1.99 <br />detector <br />detector <br />Fuel level in inches: 73.50 <br />UFT/OFT: UFT <br />Test method: FTA <br />Fuel volume In gallons: 9,962 <br />Make: RED JACKET <br />Water level in inches: 0.00 <br />Model: D.L.D. <br />Test time: 21:33-23:39 <br />S/N: 203879326 <br />Number of thermisters: 5 <br />Open time in sec: 5.00 <br />Specific gravity: 0.748 <br />Holding psi: 13 <br />Water table depth in inches: 150.00 <br />Resiliency cc: 105 <br />Determined by (method): MONTR WELL <br />Test leak rate ml/h: 252.0 <br />Leak rate in gph: -0.022 <br />Metering psi: 10 <br />Calib. leak in gph: 3.00 <br />RESULT: PASS <br />RESULT: PASS <br />COMMENTS <br />COMMENTS <br />'= ULLAGE TEST RESULTS <br />LINE <br />LINE TEST RESULTS <br />A B <br />C D <br />Test method: UTS-4 SYSTEM <br />Material: STEEL <br />Testtime: 23:45-00:25 <br />Diameter (in): <br />2.0 <br />Ullage volume: 2,038 <br />Length (in): <br />30.0 <br />Ullage pressure: 2.01 <br />Test psi: 50 <br />RESULT: PASS <br />Bleedbackcc: 0 <br />DATA FOR UTS-4T ONLY: <br />Test start time 30 <br />Time Of test 1: 23:55-00:05 <br />Test 1: start time: 22,100 <br />finish psi: 49 <br />Temperature: 71.80 <br />vol change cc: 5 <br />Flow rate: 0.200-0.200 <br />Test 2: start time: 22:10 <br />Time of test 2: 00:05-00:15 <br />finish psi: 49 <br />5 <br />Temperature: 71.70 <br />P <br />vol change cc: <br />Test 3: start time: 22:20 <br />Flow rate: 0.200-0.200 <br />finish psi: so <br />Time of test 3: 00:15-00:25 <br />vol change cc: 0 <br />Temperature: 71.70 <br />Final gph: 0.005 <br />Flow rate: 0.200-0.200 <br />RESULT: <br />PASS <br />Test type: PTK-88 <br />Pump type: PRESSURE Pump make: <br />RED JACKET <br />COMMENTS <br />COMMENTS <br />