Laserfiche WebLink
NDE'S VPLT COMPUTERIZED TANK TESTING SYSTEM Patent Pending <br />PRECISION UNDERGROUND TANK TESTING RESULTS AND CERTIFICATION <br />PAGE 1, GENERAL REPORT FORM - Copyright 1985 <br />NDE TECHNOLOGY, INC. PROPRIETARY <br />TEST DATE: 06/26/91 <br />_1. Owner of storage tanks <br />Company Representative <br />Title <br />2. Mailing address of owner <br />3. Phone of owner <br />4. STATION NUMBER <br />Location and address of <br />the tanks <br />Phone number <br />Regulatory Agency <br />5. TANK DESIGNATION OR ID # <br />6. Date each tank was tested <br />7. The name of the test method <br />8. Business name of tank <br />testing company <br />9. Mailing address of tank <br />testing company <br />Person conducting test <br />and completing report <br />License Number <br />11. Station Operator or <br />manager <br />12. Phone number <br />1.3. Owner name and <br />title <br />14. Capacity of the tank <br />15. Present or past contents <br />16. Tank construction material <br />1.7. Testing fluid <br />UNOCAL CORP. <br />Tony Yap <br />P.O. Box .5155 <br />San Ramon, CA 94583 <br />(415) 277--231.0 <br />4409 <br />1502 N. E1 Dorado Street <br />Stockton, Ca.95204 <br />(209) 464-01.19 <br />County of San Joaquin <br />Diesel <br />06/26/91 <br />VPLT COMPUTERIZED TANK TESTING SYSTEM <br />WESTERN AMERICA TANK TESTING, INC. <br />3131 FAIRHAVEN DRIVE <br />BAKERSFIELD, CA 93309 <br />Shawn Iioppes <br />92--1129 <br />N/A <br />(209) 464-0119 <br />UNOCAI, CORP. <br />1.2,000 gallons <br />Diesel <br />Fiberglass <br />Diesel <br />(TECHNICIAN) <br />18. (a) THE UNDERGROUND STORAGE TANK SYSTEM CERTIFIED TIGHT AT PRODUCT <br />HEIGHT EQUAL TO THE GRADE LEVEL. Yes. <br />(b) Allowable leak resolution of instrumentation or allowable change <br />per California Administrative Code Title 23 Waters, Chapter 3 <br />Water Resources Control Board Subchapter 16 Underground Storage <br />Regulations, Part 2643 (b), Page 4.14; 0.05 gallons per hour. <br />**# (c) MEASURED HOURLY CHANGE: LOSS (+) OR GAIN (-) GALLONS OR <br />NUMERICAL LEAK RATE IS: +0.034 Gal/Hr. <br />This measurement is within the legal limits as defined in (b). <br />NDE TECHNOLOGY, INC. PROPRIETARY <br />WATT INC. :3131 FAIRHAVEN URIVE, BAKERSFIELD, CA 93308 (805) :322-9827 <br />