Laserfiche WebLink
I./ <br />Triangle Environmental, Inc. <br />SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br />Facility: Tosco Facility # 05643 <br />Tank #: 2 Test Date: 5/18/98 <br />Product: Unleaded Premium Work#: 340690 <br />TANK TEST RESULT <br />'I est Method: <br />System 5000 <br />Capacity: <br />11855 <br />Diameter (in): <br />94 <br />Product Level (in): <br />17 <br />Liquid Volume (Gals): <br />1800 <br />Liquid Percent (%): <br />15.2% <br />Specific Gravity: <br />0.750 <br />Coef. of Expansion: <br />0.000650 <br />Water On Tank (in): <br />0 <br />Water In Tank (in): <br />0 <br />Product Temp. (F): <br />8 <br />Head Pressure (psi): <br />0.5 <br />Test Start Time: <br />9:20 PM <br />Test End Time: <br />9:21 PM <br />Test Rate (gph): <br />0.020 <br />Test Result: <br />PASS <br />Test Method: <br />ULLAGE <br />UllageVolume (gals.): <br />10055 <br />Ullage Test Time: <br />9:20 PM <br />Ullage Vacuum (psi): <br />1.4 <br />Ullage Result: <br />PASS <br />-777 LEAKDETECTOR TEST RPSUL`I""7 <br />fest Method: <br />R.J. FTA <br />Manufacturer: <br />Red Jacket <br />System Type: <br />L/D Model: <br />FX <br />50 <br />L/D Serial #: <br />010996-4280 <br />Line End Time: <br />Line Drain Back (ml): <br />110 <br />140 <br />L/D Trip Time (sec): <br />1 <br />Line Test Rate (gph): <br />Holding Pressure (psi): <br />11 <br />PASS <br />Metering Pressure (psi): <br />8 <br />L/D Test Rate (gph): <br />1.3 <br />L/D Result: <br />PASS <br />New Leak Detector? No <br />LINE TEST RESULT w <br />Test Method: <br />TEI LT -3 <br />Pump Brand: <br />Red Jacket <br />System Type: <br />Pressure <br />Line Pressure (psi): <br />50 <br />Line Start Time: <br />10:30 PM <br />Line End Time: <br />10:45 PM <br />Line Start Level: <br />140 <br />Line End Level: <br />110 <br />Line Test Rate (gph): <br />-0.032 <br />Line Test Result: <br />PASS <br />3 <br />