4. Spill/Overfiil Containment Boxes <br /> Test Method Developed By: ❑Tank Manufacturer ❑X Industry Standard ❑ Professional Engineer <br /> Test Method Used: ❑ Pressure ❑vacuum ❑X Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:±0.002 <br /> Spill Box# 87 Spill Box# 87B Spill Box# 91 Spill Box# <br /> ucket Diameter: <br /> Bucket Depth: 14" 14" 14" <br /> Wait time: 15 min 15 min 15 min 15 min <br /> Test Start Time: 10:46 10:46 10:46 <br /> Initial Reading: 0.9620 2.8790 2.7102 <br /> Test End Time: 11:01 11:01 11:01 <br /> Final Reading: 0.9604 2.8785 2.7092 <br /> Test Duration(hh:mm): 00:15 00:15 00:15 00:00 <br /> Change in Reading: -0.0016 -0.0005 -0.0010 0.0000 <br /> Pass/Fail Threshold or Criteria: ±0.002 ±0.002 ±0.002 ±0.002 <br /> Test Result: (0 Pass O fail 0 Pass Q Fail Q. Pass O Fail 0 Pass ( Fail <br /> Comments: <br /> 2 of 2 <br />