• <br /> 6. Piping Sump Testing <br /> Test Method Developed By: ❑Tank Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> Test Method Used: ❑Pressure ❑vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:±0.002 <br /> Sump# 91 Sump# Sump# Sump# <br /> Sump Diameter: 48" <br /> Sump Depth: 31" <br /> Sump Material: Fiberglass <br /> Height from Tank Top to Top of 27„ <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 24" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: ok <br /> Portion of Sump Tested 100% <br /> Does turbine shut down when <br /> sump sensor detects liquid(both 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> product and water)T <br /> Turbine shutdown response time N/A <br /> Is system programmed for fail-safe 0 Yes 0 No (O.NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> shutdown? <br /> Was fail-safe verified to be <br /> operational?' 0 Yes 0 No NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> Wait time: 15 min <br /> Test Start Time: 1:20 PM <br /> Initial Reading: 4.4964 <br /> Test End Time: 1:36 PM <br /> Final Reading: 4.4965 <br /> Test Duration(hh:mm): 00:16 00:00 00:00 00:00 <br /> Change in Reading: 0.0001 0.0000 0.0000 0.0000 <br /> Pass/Fail Threshold or Criteria: ±0.002 ±0.002 ±0.002 ±0.002 <br /> Test Result: # Pass 0 Fail 0 Pass 0 Fail 0 Pass 0 Fail 0 Pass 0 Fail <br /> Was sensor removed for testing? Q Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> Was sensor properly replaced and *Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> verified functional after testing? <br /> Comments: <br /> 4 of 7 <br />