Laserfiche WebLink
4. Spill/Overfill Containment Boxes <br /> Test Method Developed By: ❑Tank Manufacturer ❑x Industry Standard ❑Professional Engineer <br /> Test Method Used: ❑ Pressure ❑vacuum ❑X Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:±0.002 <br /> Spill Box# 871 Spill Box# 872 Spill Box# 91 Spill Box# <br /> ucket Diameter: <br /> Bucket Depth: 14 14" 14" <br /> Wait time: 15 min 15 min 15 min <br /> Test Start Time: 10:26 8:44 8:44 <br /> Initial Reading: 7.6455 7.4097 7.0264 <br /> Test End Time: 10:41 8:59 8:59 <br /> Final Reading: 7.6440 7.4091 7.0265 I+ <br /> t — <br /> Test Duration(hh:mm): 00:15 00:15 00:15 00:00 1� <br /> Change in Reading: •0.0015 -0.0006 0.0001 0.0000 <br /> Pass/Fail Threshold or Criteria: : ±0.002 { ±0.002 ±0.002 ±0.002 <br /> lestResult: ® Pass Fail OPass Fail Pass Fail <br /> Comments: The 871 (slave)spill bucket was replaced prior to testing. <br /> 2 of 2 <br />