Laserfiche WebLink
IT T S Integrity Tank Testing Syste Inc. <br /> MAR 1 7 1f <br /> PERMIT/5E�x� . <br /> Mr. Gerrit Van Riet <br /> De Boer Truck Lines, Inc. <br /> P. 0. Box 636 <br /> Ripon, California 95366 <br /> Dear Mr. Van Riet, <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets, graphs, and <br /> computer generated data for your submittal to the <br /> appropriate governmental agency. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> South 8, 000 Diesel - .0296 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> Frank J. Keser <br /> Certified Tester <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />